Issues #6988
sCtl16 in TP1.3 is in conflict with 7-4 Table B.1
Due date:
12/10/2024 (Due in 17 days)
Discuss in Upcoming Meeting:
No
Clause Reference:
Part 7-4 Table B.1
61850 Standard:
7-4
Triggering Tissue:
Final Decision:
Initial Test Document:
Updated Test Document:
Test Case ID:
Closed Reason:
--Not Set---
Triggering Tissue 2:
Triggering Tissue 3:
Description
Table B.1 is very clear that if XCBR/XSWI/Loc=T a command with orCat bay/station/remote is Not Allowed. But in sCtl16 and PIXIT Ct29 it is allowed. It seems we don't need PIXIT Ct29 because Table B.1 is very clear.
We need to rewrite sCtl16 to match Table B.1.
- the pre-condition for the first steps is XCBR/XSWI.Loc=F and CSWI.Loc is True.
- When XCBR/XSWI/Loc=T a command with orCat bay/station/remote is Not Allowed
- remove PIXIT entry CT29
Files
Related issues
Updated by Hua Qin about 2 months ago
- Related to Issues #5961: sCtl16 shall specify LocSta/MltLev to match with table B.1 added
Updated by IEC 61850 TPWG 26 days ago
- Due date set to 11/12/2024
- Status changed from New to In Progress
- Assignee set to Richard Schimmel
Accepted. Thierry and Richard to review and propose corrections.
Updated by Richard Schimmel 12 days ago
Improved version attached.