# Project Tracker ID Source Status Priority Standard(s) Subject Updated
544 IEC 61850 User Feedback Task Force Feature 25 IOP_2017/44 Closed Normal

IEC 61850-7-5

TestBlock condition implemented only in XCBR and not in any of Rxxx and Pxxx logical node 02/11/2021 07:19 AM Actions
543 IEC 61850 User Feedback Task Force Feature 24 IOP_2017/40 Closed Normal

IEC 61850-8-1

Operability issues between vendors that prevent R-SV testing between substations 02/11/2021 07:20 AM Actions
542 IEC 61850 User Feedback Task Force Feature 23 IOP_2017/38 Closed Normal

IEC 61850-6

Problem in engineering workflow due to definition of SMVsc.max 06/21/2022 09:24 AM Actions
541 IEC 61850 User Feedback Task Force Support 22 IOP_2017/36 Closed Normal

IEC 61850-9-2(LE), IEC 61869-9

APPID rules for backward compatible variants (9-2LE) shall be noted in IEC 61869-9 06/21/2022 09:24 AM Actions
540 IEC 61850 User Feedback Task Force Feature 21 IOP_2017/35 Closed Normal

IEC 61850-6

Some SCT tools are removing incomplete Inputs with ExtRef’s of serviceType=”SMV” that are used for late binding of sample values 06/21/2022 09:24 AM Actions
539 IEC 61850 User Feedback Task Force Support 20 IOP_2017/34 Closed Normal

IEC 61850-6

Relation between GCB instances in scd to the related LGOS 06/21/2022 09:24 AM Actions
521 IEC 61850 User Feedback Task Force Feature 2 IOP_2017/3 Closed Normal

IEC 61850-8-1

The GSEControl has a datSet element indicating that the gocb is configured (but with no communication entry) 06/21/2022 09:24 AM Actions
538 IEC 61850 User Feedback Task Force Support 19 IOP_2017/29 Closed Normal

IEC 61850-6

SCT engineering problems 06/21/2022 09:24 AM Actions
537 IEC 61850 User Feedback Task Force Support 18 IOP_2017/27 Closed Normal

IEC 61850-7-2, 8-1, 8-2

Server is not responding to some of the MMS requests. (see below) What should the client do this case? 06/21/2022 09:24 AM Actions
536 IEC 61850 User Feedback Task Force Support 17 IOP_2017/26 Closed Normal SCT did not import GOOSE and 3 of the sampled value control blocks that existed in PMU ICD file. This caused validation failures 06/21/2022 09:13 AM Actions
535 IEC 61850 User Feedback Task Force Support 16 IOP_2017/25 Closed Normal

6

SCD file removed unconfigured GOOSE control block but did not remove the Connected AP section contained GSE information. 06/21/2022 09:13 AM Actions
534 IEC 61850 User Feedback Task Force Feature 15 IOP_2017/24 Closed Normal

IEC 61850-6, IEC 61850-7-2

A GCB or MSVCB can only have one single control block address entry in the whole communication section 06/21/2022 09:24 AM Actions
533 IEC 61850 User Feedback Task Force Support 14 IOP_2017/23 Closed Normal MSVID shall be unique. The integrated application SCD file allowed duplicate SVID’s for two merging units. 06/21/2022 09:13 AM Actions
532 IEC 61850 User Feedback Task Force Feature 13 IOP_2017/22 Closed Normal

IEC 61850-7-2

An implementation do not allow BRCB resvTms to be written while rptEnable is True 06/21/2022 09:24 AM Actions
531 IEC 61850 User Feedback Task Force Feature 12 IOP_2017/21 Closed Normal

IEC 61850-8-1, IEC 61850-9-2

Merging Unit is not capable to publish SV outside of the recommended destination MAC address range (even though 8-1 is informative) 06/21/2022 09:24 AM Actions
530 IEC 61850 User Feedback Task Force Feature 11 IOP_2017/20 Closed Normal

IEC 61850-6

SCT is passing ICD errors to SCD. 06/21/2022 09:24 AM Actions
529 IEC 61850 User Feedback Task Force Feature 10 IOP_2017/16 Closed Normal

IEC 61850-6

SCT imports ICD with SGCB, and the settings with FC= SP outside this setting group are changed to FC=SE in the exported DOType part 06/21/2022 09:24 AM Actions
528 IEC 61850 User Feedback Task Force Feature 9 IOP_2017/15 Closed Normal

IEC 61850-6

SCD files have type defined where bType does not equal Enum or Struct, which does not follow the IEC 61850-6 description 06/21/2022 09:24 AM Actions
527 IEC 61850 User Feedback Task Force Support 8 IOP_2017/10 Closed Normal Regarding the Network infrastructure: Some MU/SAMU cannot configure their SV stream to different VLAN ID , fixed to 0 (but can c 06/21/2022 09:13 AM Actions
520 IEC 61850 User Feedback Task Force Support 1 IOP_2017/1 Closed Normal IEC 61850-6 leaves the definition of the meaning of the authentication options to the SCSM. However, neither 8-1 nor IEC 62351-6 06/21/2022 09:13 AM Actions
518 IEC 61850 User Feedback Task Force Support 34 IOP_2015 Closed Normal Does the SVID character have to be specifically mentioned to be within 10-34 characters? Some of the vendors have implemented th 06/21/2022 09:12 AM Actions
517 IEC 61850 User Feedback Task Force Support 33 IOP_2015 Closed Normal IEC 61850-9-3 slaves can by design lock themselves to IEEE C37.238 (Power Profile) masters. This is intended behavior, since IEC 06/21/2022 09:12 AM Actions
516 IEC 61850 User Feedback Task Force Support 32 IOP_2015 Closed Normal Buffered reporting testing – anomaly with resynch (write of entryId failed, but buffered reports still sent). Because of indexe 06/21/2022 09:12 AM Actions
515 IEC 61850 User Feedback Task Force Support 31 IOP_2015 Closed Normal These test cases assume that a server will send a negative response to an operate to the same value. Some servers will accept th 06/21/2022 09:12 AM Actions
514 IEC 61850 User Feedback Task Force Support 29 IOP_2015 Closed Normal Priority of error checking in controls – i.e. position-reached instead of Blocked-by-switching-hierarchy. The order of checks i 06/21/2022 09:12 AM Actions