04/16/2024

04:35 AM Client Issues #6728: cSg13 refers to PIXIT entry Sg5/Sg6 but not clarified in the expected result
I agree that current text in PIXIT entry Sg6 is Ed1 only. The SGCB attribute resvTms is optional for server, but clie... Ursula Kramarczyk

04/03/2024

08:51 AM Server Issues #6753 (Closed): sGos20, sGos21 force DUT as Subscriber to ignore future edition dataset elements, while 61850-7-1 expects achievable forward compatibility
The expected result of sGos20 and sGos21 forces the Subscriber to ignore the state change of future edition elements.... Ursula Kramarczyk

02/28/2024

06:52 AM Client Issues #6724 (Resolved): GOOSE Subscriber sGos12 test expects DUT to _send_ a GOOSE message
The expected result of mandatory sGos12 demands that DUT sends (so, it publishes) a GOOSE message. What if DUT does n... Ursula Kramarczyk

02/27/2024

07:54 AM Server Issues #6723 (Closed): GOOSE destination MAC address according Amd1: PIXIT Gs1 mismatches enhancement of sGos5
The edition 2 amendment 1 in 61850-8-1 25.3.2 and Annex B results in changes in validation of destination MAC address... Ursula Kramarczyk

02/06/2024

05:17 AM Server Issues #6697 (Closed): sRpN9 does not specify the expected access error by negative response on SetURCBValues
Basing on IEC 61850-7-2 Annex E (new in amd1) the current expected result of SetURCBValues without reservation (step ... Ursula Kramarczyk

12/11/2023

09:20 AM Server Issues #6633 (Closed): sRp15, sBr15 test description contains doName="MMXU...", while MMXU is lnClass, not doName
The test case sRp15 and sBr15 description gives in point 1 the SCL examples of following FCDA elements of a dataset:
...
Ursula Kramarczyk

11/15/2023

04:25 AM Server Issues #6541: sMdl15 allow SCL floating point value can have minor difference in DUT
The IEC 61850-7-2 defines BasicType FLOAT32 as the IEEE 754 single-precision floating point (61850-7-2 Table 2 - Basi... Ursula Kramarczyk

04/19/2023

04:38 AM Server Issues #6268: sCtl5 step 6 and step10 expected result does not apply to control objects without physical output
the cCtl5.docx proposes the last sentence of test case comments:
> The test steps 6,7 and 9,10 can not be performed ...
Ursula Kramarczyk
04:14 AM Server Issues #6320 (Closed): Ct24 description uses not defined in the standard term: Internal Controllable Objects
the Ct24 uses in the description capitalized written _Internal Controllable Objects_. There is no definition of this ... Ursula Kramarczyk