# Project Tracker ID Source Status Priority Standard(s) Subject Updated
480 IEC 61850 User Feedback Task Force Support 36 IOP_2013 Closed Normal A different client made use of a URCB that had been reserved in SCL for use by a different client via ClientLN. Currently, there 06/21/2022 09:00 AM Actions
484 IEC 61850 User Feedback Task Force Support 40 IOP_2013 Closed Normal A question was raised in regards can Report EntryIDs be reused after IED restart. If so, guidance needs to be given for system d 06/21/2022 09:00 AM Actions
481 IEC 61850 User Feedback Task Force Support 37 IOP_2013 Closed Normal A question was raised in regards to how a client should resynchronize to receive the last report (Buffered Reporting). The sta 06/21/2022 09:00 AM Actions
483 IEC 61850 User Feedback Task Force Support 39 IOP_2013 Closed Normal A question was raised in regards to the expected behavior of a server/BRCB that has been purged (e.g. no events buffered) and th 06/21/2022 09:00 AM Actions
419 IEC 61850 User Feedback Task Force Support 10.2 ENTSO-E Closed Normal

IEC 61850-7-2

Also many other features of GOOSE messaging are left to the manufacturer to choose. 12/06/2022 09:01 AM Actions
472 IEC 61850 User Feedback Task Force Support 28 IOP_2013 Closed Normal An ED.2 SCT would not import an ED.1 SCL file. This needs to be addressed with rules of transformation and the definition of a s 06/21/2022 09:00 AM Actions
488 IEC 61850 User Feedback Task Force Support 3 IOP_2015 Closed Normal

6

An ICD file has predefined ReportControlBlock. With the SCT we attached a dataset to one URCB. Afterwards we decide to de-config 06/21/2022 09:11 AM Actions
493 IEC 61850 User Feedback Task Force Support 8 IOP_2015 Closed Normal

6

An icd/iid file is not required to include the “original SCL” element. Is it required to be added to the IED instance in the SCD 06/21/2022 09:12 AM Actions
486 IEC 61850 User Feedback Task Force Support 1 IOP_2015 Closed Normal

7-1, 7-4

An ICT has required LGOS configuration coming from SCT to be able to subscribe GOOSE. Is it the way it should work? And is it re 06/21/2022 09:11 AM Actions
470 IEC 61850 User Feedback Task Force Support 26 IOP_2013 Closed Normal An ICT provides an IID/ICD file that defines 4 GOCBs. The SCT imports this file, creates an SCD which has only 1 GOCB. The ICT r 06/21/2022 09:00 AM Actions
479 IEC 61850 User Feedback Task Force Support 35 IOP_2013 Closed Normal An SCL file was produced that had a GOOSE DataSet that contained members that had FC=CO and FC=CF. The SCT performing the import 06/21/2022 09:00 AM Actions
473 IEC 61850 User Feedback Task Force Support 29 IOP_2013 Closed Normal An SCL file was provided that had a <Val> for an OctetString value. A question was raised as to the correct format for the value 06/21/2022 09:00 AM Actions
541 IEC 61850 User Feedback Task Force Support 22 IOP_2017/36 Closed Normal

IEC 61850-9-2(LE), IEC 61869-9

APPID rules for backward compatible variants (9-2LE) shall be noted in IEC 61869-9 06/21/2022 09:24 AM Actions
583 IEC 61850 User Feedback Task Force Support 55 ENTSO-E Closed Normal

IEC 61850-7-4

Autoreclosure: Autoreclosure - 3ph closing command missing 12/06/2022 09:38 AM Actions
516 IEC 61850 User Feedback Task Force Support 32 IOP_2015 Closed Normal Buffered reporting testing – anomaly with resynch (write of entryId failed, but buffered reports still sent). Because of indexe 06/21/2022 09:12 AM Actions
558 IEC 61850 User Feedback Task Force Support 30 ENTSO-E Closed Normal

IEC 61850-7-4

Busbar protection (BBP): Diff/Kirchoff BBP 12/06/2022 09:02 AM Actions
559 IEC 61850 User Feedback Task Force Support 31 ENTSO-E Closed Normal

IEC 61850-7-4

Busbar protection: ARC detection protection 12/06/2022 09:02 AM Actions
560 IEC 61850 User Feedback Task Force Support 32 ENTSO-E Closed Normal

IEC 61850-7-4

Busbar protection: Simplified logic 02/11/2021 07:02 AM Actions
433 IEC 61850 User Feedback Task Force Support 24 ENTSO-E Closed Normal

IEC 61850-10

Client implementation Level A certification 02/11/2021 07:08 AM Actions
423 IEC 61850 User Feedback Task Force Support 14 ENTSO-E Closed Normal Conformance test for SICS. 02/11/2021 07:47 AM Actions
476 IEC 61850 User Feedback Task Force Support 32 IOP_2013 Closed Normal Currently, in SCL, the size of an array is numeric. This could lead to issues of consistency (e.g. one having 32 array elements 06/21/2022 09:00 AM Actions
418 IEC 61850 User Feedback Task Force Support 10.1 ENTSO-E Closed Normal

IEC 61850-6

DataSets for GOOSE messaging - modeling with: only DA, only DO or both? 02/11/2021 08:02 AM Actions
489 IEC 61850 User Feedback Task Force Support 4 IOP_2015 Closed Normal

6

Declaration of Clients in an SCL file: The icd/iid file of a client only device can have a LN at the level of the access point. 06/21/2022 09:11 AM Actions
491 IEC 61850 User Feedback Task Force Support 6 IOP_2015 Closed Normal

6

Declaration of CtlModel for controllable CDCs (a) If a device does not support configuration of the ctlModel for a specific DO – 06/21/2022 09:11 AM Actions
552 IEC 61850 User Feedback Task Force Support 33 IOP_2017/54 Resolved Normal

IEC 61850-9-3

Disruption of network when TC are not set to the correct domain 05/09/2023 09:32 AM Actions
(76-100/3050) Per page: 25, 50, 100