Project

General

Profile

Issues

Filters

Apply Clear

# Project Tracker ID Source Status Priority Standard(s) Subject Updated
503 IEC 61850 User Feedback Task Force Support 18 IOP_2015 Closed Normal

6

Issue 1: History section is present in ICD but during import SCT is discarding this history section. Also, maintenance of histor 06/21/2022 09:12 AM Actions
502 IEC 61850 User Feedback Task Force Support 17 IOP_2015 Closed Normal

6

Issue 1: During import of SSD file SST/SCT is not able to recognize Busbar connection node. It is connectivity node and there i 06/21/2022 09:12 AM Actions
501 IEC 61850 User Feedback Task Force Support 16 IOP_2015 Closed Normal

6

PAUL MYRDA: In SCL it is possible to define unbuffered report control blocks with indexed set to false but with max instances se 06/21/2022 09:12 AM Actions
500 IEC 61850 User Feedback Task Force Support 15 IOP_2015 Closed Normal

6

2.2. BufMod is optional for ReportControl. No default value provided by the schema. SCT is interpreting as unbuffered only. Com 06/21/2022 09:12 AM Actions
499 IEC 61850 User Feedback Task Force Support 14 IOP_2015 Closed Normal

6

Issue 4 – Private section – namespace moved from SCL node to Private nodes ICT added the namespace within the privates instead o 06/21/2022 09:12 AM Actions
498 IEC 61850 User Feedback Task Force Support 13 IOP_2015 Closed Normal

6

Issue 3 – GoCB confRev - behaviour if ConfRev=“0“ IED rejected that value. 7-2: If there are inconsistent attribute values in t 06/21/2022 09:12 AM Actions
497 IEC 61850 User Feedback Task Force Support 12 IOP_2015 Closed Normal

6

Issue 2 - IED restrictions not known by SCT 2.1 IED support 50% URCB and 50% BRCB Service section provide a total RCB number 2. 06/21/2022 09:12 AM Actions
496 IEC 61850 User Feedback Task Force Support 11 IOP_2015 Closed Normal

6

DUSTIN: Issue 3: Symmetrical Bindings of DA In case of late Binding at DO/DA Level. IED expects DO at later binding, but source 06/21/2022 09:12 AM Actions
495 IEC 61850 User Feedback Task Force Support 10 IOP_2015 Closed Normal

6

Issue 2: SCT Behavior When Revising/Replacing IED Configuration Between SCT Tools In terms of the data model structure and comm 06/21/2022 09:12 AM Actions
494 IEC 61850 User Feedback Task Force Support 9 IOP_2015 Closed Normal

6

DUSTIN: Issue 1: X/Y Coordinates Upon exchanging the SCD file between SCT tools, the drawing/visualization of the single line d 06/21/2022 09:12 AM Actions
493 IEC 61850 User Feedback Task Force Support 8 IOP_2015 Closed Normal

6

An icd/iid file is not required to include the “original SCL” element. Is it required to be added to the IED instance in the SCD 06/21/2022 09:12 AM Actions
492 IEC 61850 User Feedback Task Force Support 7 IOP_2015 Closed Normal

6

(a) If a device does not support configuration of the ctlModel for a specific DO – what is the correct way to declare this? • De 06/21/2022 09:12 AM Actions
491 IEC 61850 User Feedback Task Force Support 6 IOP_2015 Closed Normal

6

Declaration of CtlModel for controllable CDCs (a) If a device does not support configuration of the ctlModel for a specific DO – 06/21/2022 09:11 AM Actions
490 IEC 61850 User Feedback Task Force Support 5 IOP_2015 Closed Normal

6

In the service section, an IED can declare “modify dataset” to be FALSE. That means, datasets in the IED cannot be changed by th 06/21/2022 09:11 AM Actions
489 IEC 61850 User Feedback Task Force Support 4 IOP_2015 Closed Normal

6

Declaration of Clients in an SCL file: The icd/iid file of a client only device can have a LN at the level of the access point. 06/21/2022 09:11 AM Actions
488 IEC 61850 User Feedback Task Force Support 3 IOP_2015 Closed Normal

6

An ICD file has predefined ReportControlBlock. With the SCT we attached a dataset to one URCB. Afterwards we decide to de-config 06/21/2022 09:11 AM Actions
487 IEC 61850 User Feedback Task Force Support 2 IOP_2015 Closed Normal

6

In the service section, there is the new element “client services”. That element includes GOOSE (default FALSE). Is it required 06/21/2022 09:11 AM Actions
486 IEC 61850 User Feedback Task Force Support 1 IOP_2015 Closed Normal

7-1, 7-4

An ICT has required LGOS configuration coming from SCT to be able to subscribe GOOSE. Is it the way it should work? And is it re 06/21/2022 09:11 AM Actions
507 IEC 61850 User Feedback Task Force Support 22 IOP_2015 Closed Normal If the client reads a SCD file and loads then the data model (or vice versa ???) what data shall a client compare? confRef’s, da 06/21/2022 09:10 AM Actions
513 IEC 61850 User Feedback Task Force Support 28 IOP_2015 Closed Normal

90-4

HSR and PRP are redundancy protocols. In order to prevent a single point of failure, many people are considering 2 red boxes 06/21/2022 09:09 AM Actions
456 IEC 61850 User Feedback Task Force Support 13 IOP_2013 Closed Normal A client only ICD did not have a ClientServices section. An SCT imported the file and assigned used the IED to reserve a RCB wit 06/21/2022 09:00 AM Actions
485 IEC 61850 User Feedback Task Force Support 41 IOP_2013 Closed Normal Some switches discard the IEEE 802.1Q tag known as VLAN 0 on packets sent/received on the trunk ports. Others discard the packet 06/21/2022 09:00 AM Actions
484 IEC 61850 User Feedback Task Force Support 40 IOP_2013 Closed Normal A question was raised in regards can Report EntryIDs be reused after IED restart. If so, guidance needs to be given for system d 06/21/2022 09:00 AM Actions
483 IEC 61850 User Feedback Task Force Support 39 IOP_2013 Closed Normal A question was raised in regards to the expected behavior of a server/BRCB that has been purged (e.g. no events buffered) and th 06/21/2022 09:00 AM Actions
482 IEC 61850 User Feedback Task Force Support 38 IOP_2013 Closed Normal When should buffering start for a reserved and fully configured BRCB. The discussion was that buffering should probably begin up 06/21/2022 09:00 AM Actions
(126-150/3048) Per page: 25, 50, 100

Also available in: Atom CSV PDF