Project

General

Profile

Issues

Filters

Apply Clear

# Project Tracker ID Source Status Priority Standard(s) Subject Updated
532 IEC 61850 User Feedback Task Force Feature 13 IOP_2017/22 Closed Normal

IEC 61850-7-2

An implementation do not allow BRCB resvTms to be written while rptEnable is True 06/21/2022 09:24 AM Actions
585 IEC 61850 User Feedback Task Force Feature 1337 IOP_2019 Closed Normal

IEC 61850-6

SCT unable to configure the device to communicate on multiple subnets due to having a single AP (with all Eth. Ports) 07/05/2022 08:24 AM Actions
586 IEC 61850 User Feedback Task Force Feature 1340 IOP_2019 Closed Normal

IEC 61850-6

Client application cannot connect to IED that are having issue with format of AP-Title 07/05/2022 08:26 AM Actions
457 IEC 61850 User Feedback Task Force Feature 14 IOP_2013 Closed Normal

IEC 61850-6

A SCL file is created without maxAttributes attribute defined. What does it mean semantically it the attr. is missing? 02/11/2021 07:46 AM Actions
587 IEC 61850 User Feedback Task Force Feature 1404 IOP_2019 Closed Normal

IEC 61850-6

LNodeTypes and DOTypes not used in the IED section - is it allowed to keep them in DataTypeTemplate section? 02/11/2021 07:01 AM Actions
534 IEC 61850 User Feedback Task Force Feature 15 IOP_2017/24 Closed Normal

IEC 61850-6, IEC 61850-7-2

A GCB or MSVCB can only have one single control block address entry in the whole communication section 06/21/2022 09:24 AM Actions
588 IEC 61850 User Feedback Task Force Feature 1548 IOP_2019 Closed Normal

IEC 61850-6

More than one redundant PhysConn for ConnectedAP of IED AP and no redundant PhysConn on same AP 06/21/2022 09:28 AM Actions
593 IEC 61850 User Feedback Task Force Feature 1601 IOP_2019 Closed Normal

IEC 61850-6

How to disable SV control blocks that are not in use? 06/21/2022 09:29 AM Actions
594 IEC 61850 User Feedback Task Force Feature 1642_01 IOP_2019 Closed Normal

IEC 61850-6

Reverse engineering of subscription is not possible when Server and ServerAt APs are connected to the same SubNetwork 06/21/2022 09:29 AM Actions
595 IEC 61850 User Feedback Task Force Feature 1642_04 IOP_2019 Closed Normal

IEC 61850-7-1

How does the SCT know whether to configure the LSVS.SvCBRef (if it is not configured)? 06/21/2022 09:29 AM Actions
589 IEC 61850 User Feedback Task Force Feature 1700 IOP_2019 Closed Normal

IEC 61850-6

Usage of max of RptEnabled when indexed attribute is false and the relationship to RptEnabled 07/05/2022 08:28 AM Actions
596 IEC 61850 User Feedback Task Force Feature 1710 IOP_2019 Closed Normal An IED declares constraints that are not machine processable 02/11/2021 06:43 AM Actions
602 IEC 61850 User Feedback Task Force Feature 1742 IOP_2019 Resolved Normal

IEC 61850-9-3

Merging Unit standard requires MU clock to jump on PTP time jumps, which is not true for Boundary Clocks. 05/09/2023 09:32 AM Actions
590 IEC 61850 User Feedback Task Force Feature 1800 IOP_2019 Resolved Normal

IEC 61850-6

ICT fails to check validity of the SCD file regarding the IED constraints 11/07/2023 08:22 AM Actions
591 IEC 61850 User Feedback Task Force Feature 1857 IOP_2019 Closed Normal

IEC 61850-6

A reservation could not be made via SCL for an IED’s report due to the lack of a ConnectedAP associated with the client’s AP 07/05/2022 08:34 AM Actions
600 IEC 61850 User Feedback Task Force Feature 1947 IOP_2019 Closed Normal

IEC 61850-7-1

Connect the ExtRef - different supported mechanisms by ICT 06/21/2022 09:29 AM Actions
521 IEC 61850 User Feedback Task Force Feature 2 IOP_2017/3 Closed Normal

IEC 61850-8-1

The GSEControl has a datSet element indicating that the gocb is configured (but with no communication entry) 06/21/2022 09:24 AM Actions
404 IEC 61850 User Feedback Task Force Feature 2.1 ENTSO-E Closed Normal Meaning of "optional" regarding data model 02/11/2021 06:21 AM Actions
405 IEC 61850 User Feedback Task Force Feature 2.2 ENTSO-E Closed Normal Optionality of DO/DA from the point of view of users 02/11/2021 06:20 AM Actions
463 IEC 61850 User Feedback Task Force Feature 20 IOP_2013 Closed High

IEC 61850-6

GOOSE suscription: managing data types in datasets 02/11/2021 05:56 AM Actions
540 IEC 61850 User Feedback Task Force Feature 21 IOP_2017/35 Closed Normal

IEC 61850-6

Some SCT tools are removing incomplete Inputs with ExtRef’s of serviceType=”SMV” that are used for late binding of sample values 06/21/2022 09:24 AM Actions
598 IEC 61850 User Feedback Task Force Feature 2108 IOP_2019 Closed Normal

IEC 61850-6

The SCT tool creates an invalid ReportControl element 07/05/2022 08:47 AM Actions
542 IEC 61850 User Feedback Task Force Feature 23 IOP_2017/38 Closed Normal

IEC 61850-6

Problem in engineering workflow due to definition of SMVsc.max 06/21/2022 09:24 AM Actions
543 IEC 61850 User Feedback Task Force Feature 24 IOP_2017/40 Closed Normal

IEC 61850-8-1

Operability issues between vendors that prevent R-SV testing between substations 02/11/2021 07:20 AM Actions
544 IEC 61850 User Feedback Task Force Feature 25 IOP_2017/44 Closed Normal

IEC 61850-7-5

TestBlock condition implemented only in XCBR and not in any of Rxxx and Pxxx logical node 02/11/2021 07:19 AM Actions
(26-50/3048) Per page: 25, 50, 100