Project

General

Profile

Support #6303

LN PDIF – setting for nominal current

Added by Maud Merley about 1 year ago. Updated 11 months ago.

Status:
Resolved
Priority:
Normal
Category:
Standard clarification required
Start date:
03/28/2023
Due date:
% Done:

0%

Estimated time:
ID:
Source:
RTE
TF Unique ID:
WG10 Proposal:
Estimated Completion:
Discuss in Upcoming Meeting:
No
To discuss in WG10:
No
Short Proposal:

Send the issue to 7-500

Standard(s):

IEC 61850-7-500

Needs More Information:
No
Assigned TF:

Description

LN PDIF contains DO LoSet and HiSet which represent Low (resp High) operate value setting [%] relative to the nominal current.
As the nominal current is not a setting in PDIF, how could a user set the value of the threshold for minimal (resp. maximal) differential current ?

In practice, the base current for PDIF is often the highest primary nominal current of the associated TC.


Files


Proposal descriptions

We need the use case from a modelling perspective following the definition of the DOs.


Related issues

Copied to 61850-7-5 and 61850-7-500 - IEC61850-7-5 #6376: LN PDIF – setting for nominal currentNew03/28/2023