05/06/2025
- 09:51 AM IEC 61850 User Feedback Task Force Improvement #7199: Addition of a DO representing the acoustic noise
- Precisions on the use case : The transformer noise is inconfortable for neighborhood. The noise is measured by a sens...
- 03:46 AM IEC 61850 User Feedback Task Force Feature #7204 (New): New DO for measuring the circulating current between two tap changer position
- During the operation of on load tap changers, there will be an instant of time when the rotary switch will connect tw...
05/05/2025
- 07:42 AM IEC 61850 User Feedback Task Force Feature #7203 (New): DOs for moisture level and oil pressure measurement
- There is no DO representing the moisture level of dehydrating breathers (silicagel) used for oil insulated equipments...
- 07:37 AM IEC 61850 User Feedback Task Force Feature #7202 (Triage): Include more DO in LN PSCH to send signals
- In the DO available for teleprotection in LN PSCH, there is only blocking, permission and trip.
The following infor... - 07:32 AM IEC 61850 User Feedback Task Force Feature #7201 (New): New DA to indicate the fabrication year of the device
- In the device name plate (DPL), there is no attribute allowing to indicate the fabrication year of the device.
- 07:30 AM IEC 61850 User Feedback Task Force Feature #7200 (New): Modeling of air salinity
- There is no DO modelling the air salinity.
Use case: Monitoring of air salinity is employed to estimate corrosion an... - 07:27 AM IEC 61850 User Feedback Task Force Improvement #7199 (New): Addition of a DO representing the acoustic noise
- Add a new DO for Measured Value and an other DO for Alarm and its corresponding threshold.
Use case: monitoring of... - 07:15 AM IEC 61850 User Feedback Task Force Improvement #7198 (Resolved): SwgTmms description not meaningful
- In LN RPSB, the semantic of "SwgTmms" does not properly reflect that this is a time window. There is a possible risk ...
- 07:06 AM IEC 61850 User Feedback Task Force Improvement #7197 (Resolved): Inconsistency of DO in LN SARC
- Today, in LN SARC, there is FADet and SwArcDet. Based on the dictionnary, A is for current. For this reason FADet sho...
01/08/2025
- 04:57 AM IEC 61850 User Feedback Task Force Improvement #7095 (Closed): DO "CECtl" and "Auto" of LN CCGR share a close semantic description
- In IEC 61850-7-4, the LN CCGR contains 2 DO called "CECtl" and "Auto" (CDC SPC) sharing a close semantic description ...