Include more DO in LN PSCH to send signals

Added by Christophe Ghafari about 18 hours ago.

Status:
New
Priority:
Normal
Assignee:
-
Category:
-
Start date:
05/05/2025
Due date:
% Done:

0%

Estimated time:
ID:
Source:
TF Unique ID:
WG10 Proposal:
Estimated Completion:
Discuss in Upcoming Meeting:
Yes
To discuss in WG10:
No
Short Proposal:
Standard(s):

IEC 61850-7-4

Needs More Information:
No
Assigned TF:
None

Description

In the DO available for teleprotection in LN PSCH, there is only blocking, permission and trip.
The following information also exist and need to be added:
- disable of recloser cycle
- closing order of circuit breaker
- transmission of a generic boolean information

Use cases:
PSCH groups applications sending signals to other line ends.
Disable of recloser cycle : an application identifies a fault on an underground cable. Reclosing should not happen in this case. The most consistent approach would be to add a DO TxDisable, RxDisable to PSCH.
Closing order of circuit breaker : in some cases, substation level automatons send closing orders to the other line end. The most consistent approach would be to add a DO TxCls, RxCls to PSCH.
Generic information : in some cases, substation level automatons send generic boolean information to the other line end, e.g. position of cb. The most consistent approach would be to add a DO TxOnOff, RxOnOff to PSCH.