Description
During the operation of on load tap changers, there will be an instant of time when the rotary switch will connect two different contacts at the same time yielding a circulating current to flow. This current can be measured by a sensor and be monitored for predictive maintenance (to estimate when changing the rotary switch is necessary). The commutation time should be added as well.
Proposal descriptions
Two new DO in LN SLTC :
- One for circulating current
- One for commutation time