Support #6303

LN PDIF – setting for nominal current

Added by Maud Merley over 1 year ago. Updated over 1 year ago.

Status:
Resolved
Priority:
Normal
Category:
Standard clarification required
Start date:
03/28/2023
Due date:
% Done:

0%

Estimated time:
ID:
Source:
RTE
TF Unique ID:
WG10 Proposal:
Estimated Completion:
Discuss in Upcoming Meeting:
No
To discuss in WG10:
No
Short Proposal:

Send the issue to 7-500

Standard(s):

IEC 61850-7-500

Needs More Information:
No
Assigned TF:

Description

LN PDIF contains DO LoSet and HiSet which represent Low (resp High) operate value setting [%] relative to the nominal current.
As the nominal current is not a setting in PDIF, how could a user set the value of the threshold for minimal (resp. maximal) differential current ?

In practice, the base current for PDIF is often the highest primary nominal current of the associated TC.


Files


Proposal descriptions

We need the use case from a modelling perspective following the definition of the DOs.


Related issues

Copied to 61850-7-5 and 61850-7-500 - IEC61850-7-5 #6376: LN PDIF – setting for nominal currentNew03/28/2023

Actions
#1

Updated by Vladan Cvejic over 1 year ago

  • Discuss in Upcoming Meeting changed from No to Yes
#2

Updated by Thierry Dufaure over 1 year ago

I guees, that the setting LoSet and HiSet apply the differential protection for power transformer:
LoSet would define the threhold in % for IDiff/InominalAtLowVoltageSide
HiSet would define the threhold in % for IDiff/InominalAtHighVoltageSide

The nominal current of the power transformer is determined by the setting YPTR.VARtg and
- YLTC.HiVRtg for the current at the high voltage side of the power transformer
- YLTC.LoVRtg for the current at the low voltage side of the power transformer

For differential protection for line: the rated current is given at the TCTR.ARtg. However, it is not clear to me if LoSet or HiSet apply to the Line Differentail Protection.

#3

Updated by Carlos Rodriguez del Castillo over 1 year ago

  • Category set to Standard clarification required
  • Status changed from New to Resolved
  • Assignee set to Christophe Ghafari
  • Discuss in Upcoming Meeting changed from Yes to No
  • Proposal descriptions updated (diff)
  • Short Proposal set to Send the issue to 7-500
  • Standard(s) set to IEC 61850-7-500

Decision:
- Send the issue to 7-500 as they have the experts to do it.

#4

Updated by Michael Haecker over 1 year ago

I would like to offer another protection application related explanation, valid for both transformer differential protection and line differential protection.

The two setting parameters model two points in the tripping characteristic of differential protections.

'LoSet' refers to "Id.LS" in the attached figure, which is the lowest setting possible.
'HiSet' refers to "Id.LS" which is the level of differential current from when on a trip shall occur without restraining.

In the description texts, both parameters are "relative to the nominal current", where in implementations often a chosen "reference current" is used instead (to be independent from the CT nominal current etc.). A "reference current" setting is not modelled in PDIF LN class.

#5

Updated by Keith Gray over 1 year ago

I spoke to one of our protection engineering SMEs and received some more details.

They agreed with the plot that Michael shows in his comment. There are typically two different elements set. One, the Low Set, is for the slope differential. The other, the High Set, is for the instantaneous differential.

Based on the AtMostOne constraint, it appears as if it was intended that two PDIF elements would be used, one for the slope differential and one for the instantaneous differential.

As far as the nominal current, they said that different vendors or relays may set their differential elements using different nominal currents. One relay may use CT current rating as nominal current. Another relay may use the transformer (or some other protected apparatus) rated current as the nominal (I may not have the terms exactly correct here).

They did agree that having a nominal current setting would be useful. However, it has to be general enough that it can apply to the various values used by the different vendors.

#6

Updated by Thierry Dufaure over 1 year ago

Thierry Dufaure wrote in #note-2: - Typo for the HiVRtg / LoVRtg - they are both located in YPTR

I guees, that the setting LoSet and HiSet apply the differential protection for power transformer:
LoSet would define the threhold in % for IDiff/InominalAtLowVoltageSide
HiSet would define the threhold in % for IDiff/InominalAtHighVoltageSide

The nominal current of the power transformer is determined by the setting YPTR.VARtg and
- YPTR.HiVRtg for the current at the high voltage side of the power transformer
- YPTR.LoVRtg for the current at the low voltage side of the power transformer

For differential protection for line: the rated current is given at the TCTR.ARtg. However, it is not clear to me if LoSet or HiSet apply to the Line Differentail Protection.

#7

Updated by Carlos Rodriguez del Castillo over 1 year ago

  • Discuss in Upcoming Meeting changed from No to Yes
#8

Updated by Carlos Rodriguez del Castillo over 1 year ago

  • Discuss in Upcoming Meeting changed from Yes to No

The solution should follow Standard 60255-187.

#9

Updated by Carlos Rodriguez del Castillo over 1 year ago

  • Discuss in Upcoming Meeting changed from No to Yes
#10

Updated by Carlos Rodriguez del Castillo over 1 year ago

  • Discuss in Upcoming Meeting changed from Yes to No
#11

Updated by Vladan Cvejic over 1 year ago