sCtl16 shall specify LocSta/MltLev to match with table B.1

Added by Richard Schimmel over 1 year ago. Updated about 2 months ago.

Status:
Closed
Priority:
Normal
Due date:
12/13/2022
Discuss in Upcoming Meeting:
No
Clause Reference:
Table B.1
61850 Standard:
7-4
Triggering Tissue:
Final Decision:
Initial Test Document:
Updated Test Document:
Test Case ID:
Closed Reason:
--Not Set---
Triggering Tissue 2:
Triggering Tissue 3:

Description

1) Table B.1 is very clear how a device shall respond in case for all combinations of XCBR.Loc + CSWI.Loc+ CSWI.LocSta + LLN0.MltLev and orCat=Bay/Station/Remote. sCtl16 does not specify LocSta and MltLev and as such the expected result can be wrong. For example SBOes step 3 expect response+ this requires LocSta=T! What if LocSta is not present?

2) What is the default value for LocSta when it's not present in the datamodel? I assume LocSta=False then the expected result for step 3 is wrong.

3) Because table B.1 is very specific, why do we have a PIXIT entry for SBOes step 6?

Let's discuss at TPWG