Issues #6617
tIieN1 - can a popup warning be considered as 'not allowed'
Due date:
10/29/2024 (Due in 16 days)
Discuss in Upcoming Meeting:
No
Clause Reference:
61850 Standard:
6
Triggering Tissue:
Final Decision:
Initial Test Document:
Updated Test Document:
Test Case ID:
Closed Reason:
--Not Set---
Triggering Tissue 2:
Triggering Tissue 3:
Description
I see ICT tools that also provide some SCT features. Such tools may have a setting to allow or block SCT features. For example when SCT features are blocked the data model can't change and tIieN1 will pass. When the setting allows SCT features the tIieN1 will fail. So the test result depends on a setting. Which is very common for server testing and allowed.
Now what if an ICT tool does not have such setting but instead pop-ups with a warning and ask the engineer something like "dataobject/LN is allocated to a client. are you sure to remove?". Is this acceptable to pass the test?
Files