Issues #6617
tIieN1 - can a popup warning be considered as 'not allowed'
Description
I see ICT tools that also provide some SCT features. Such tools may have a setting to allow or block SCT features. For example when SCT features are blocked the data model can't change and tIieN1 will pass. When the setting allows SCT features the tIieN1 will fail. So the test result depends on a setting. Which is very common for server testing and allowed.
Now what if an ICT tool does not have such setting but instead pop-ups with a warning and ask the engineer something like "dataobject/LN is allocated to a client. are you sure to remove?". Is this acceptable to pass the test?
Files
Updated by IEC 61850 TPWG 11 months ago
- Due date set to 01/09/2024
- Status changed from New to Resolved
Many tools on the market provide some mix of ICT and SCT function. UCA needs to address these products.
Richard to review and propose resolution.
Updated by IEC 61850 TPWG 3 months ago
- Due date changed from 01/09/2024 to 09/03/2024
- Status changed from Resolved to In Progress
- Assignee set to Richard Schimmel
Any implementation that prevents changing of data model in the output SCL is acceptable.
Updated by Zach Wormgoor 2 months ago
- File Proposal to accommodate dual role ICT SCT tools.docx Proposal to accommodate dual role ICT SCT tools.docx added
Attached is a detailed proposal to allow flexibility for ICTs, with the intent of better user experience and better engineering workflow.
Updated by IEC 61850 TPWG 2 months ago
- Due date changed from 09/03/2024 to 09/17/2024
Generally accept proposal, but further discussion of SED/Exchange between 2 SCTs needs further discussion.
Updated by IEC 61850 TPWG 11 days ago
- Due date changed from 10/29/2024 to 11/12/2024
- Assignee changed from Richard Schimmel to Camille Bloch
This needs to be reviewed in context of engineering process. Thierry and Camille to discuss.