Project

General

Profile

Issues #6268

sCtl5 step 6 and step10 expected result does not apply to control objects without physical output

Added by Hua Qin about 1 year ago. Updated 28 days ago.

Status:
Closed
Priority:
Normal
Due date:
05/02/2023
Discuss in Upcoming Meeting:
No
Clause Reference:
61850 Standard:
Triggering Tissue:
Final Decision:
Initial Test Document:
Updated Test Document:
Test Case ID:
sCtl5
Closed Reason:
--Not Set---
Triggering Tissue 2:
Triggering Tissue 3:

Description

For the device which supports test/blocked and blocked and only internal control objects without physical outputs, the sCtl5 step 6 and step 10 does not apply.

Suggest to update the expected result for step 6 and step 10 to:

Commands are accepted.
For control objects with wired physical outputs, the outputs are blocked, DUT sends CommandTermination with AddCause = blocked-by-mode.
For control objects without wired physical outputs, command is executed.


Files

sCtl5.docx sCtl5.docx 23.3 KB Thierry Dufaure, 04/03/2023 08:26 AM
sCtl5_210423.docx sCtl5_210423.docx 23.4 KB Thierry Dufaure, 04/21/2023 04:47 AM

Also available in: Atom PDF