Project

General

Profile

Issues #6268

Updated by Hua Qin about 1 year ago

For the device which supports test/blocked and blocked and only internal control objects without physical outputs, the sCtl5 step 6 and step 10 does not apply. 

 Suggest to update the expected result for step 6 and step 10 to: 

 Commands are accepted. 
 For control objects with wired physical outputs, the outputs are blocked, DUT sends CommandTermination with AddCause = blocked-by-mode. 
 For control objects without wired physical outputs, command is executed. DUT sends CommandTermination+ 

Back