# Project Tracker ID Source Status Priority Standard(s) Subject Updated
419 IEC 61850 User Feedback Task Force Support 10.2 ENTSO-E Closed Normal

IEC 61850-7-2

Also many other features of GOOSE messaging are left to the manufacturer to choose. 12/06/2022 09:01 AM Actions
417 IEC 61850 User Feedback Task Force Support 9 ENTSO-E Closed Normal

6-100

There is no mechanism proposed by the Standard to positively identify data points in the data model. For instance PTOC can refer 12/06/2022 09:01 AM Actions
555 IEC 61850 User Feedback Task Force Support 2 H30 Rejected Normal Link Failover reliability problem - implication to protection application 10/25/2022 09:01 AM Actions
541 IEC 61850 User Feedback Task Force Support 22 IOP_2017/36 Closed Normal

IEC 61850-9-2(LE), IEC 61869-9

APPID rules for backward compatible variants (9-2LE) shall be noted in IEC 61869-9 06/21/2022 09:24 AM Actions
539 IEC 61850 User Feedback Task Force Support 20 IOP_2017/34 Closed Normal

IEC 61850-6

Relation between GCB instances in scd to the related LGOS 06/21/2022 09:24 AM Actions
538 IEC 61850 User Feedback Task Force Support 19 IOP_2017/29 Closed Normal

IEC 61850-6

SCT engineering problems 06/21/2022 09:24 AM Actions
537 IEC 61850 User Feedback Task Force Support 18 IOP_2017/27 Closed Normal

IEC 61850-7-2, 8-1, 8-2

Server is not responding to some of the MMS requests. (see below) What should the client do this case? 06/21/2022 09:24 AM Actions
440 IEC 61850 User Feedback Task Force Support 3 Vattenfall Closed Normal The specified sigal has a utility process name independent of used protcol. E.g. "start of distance protection". Also link to a 06/21/2022 09:19 AM Actions
523 IEC 61850 User Feedback Task Force Support 4 IOP_2017/6 Closed Normal

IEC 61850-6

The R-GOOSE test area SCD was created by importing an ICD that was of schema 2007 B3. It exported 2007 B2 without removing/down 06/21/2022 09:16 AM Actions
536 IEC 61850 User Feedback Task Force Support 17 IOP_2017/26 Closed Normal SCT did not import GOOSE and 3 of the sampled value control blocks that existed in PMU ICD file. This caused validation failures 06/21/2022 09:13 AM Actions
535 IEC 61850 User Feedback Task Force Support 16 IOP_2017/25 Closed Normal

6

SCD file removed unconfigured GOOSE control block but did not remove the Connected AP section contained GSE information. 06/21/2022 09:13 AM Actions
533 IEC 61850 User Feedback Task Force Support 14 IOP_2017/23 Closed Normal MSVID shall be unique. The integrated application SCD file allowed duplicate SVID’s for two merging units. 06/21/2022 09:13 AM Actions
527 IEC 61850 User Feedback Task Force Support 8 IOP_2017/10 Closed Normal Regarding the Network infrastructure: Some MU/SAMU cannot configure their SV stream to different VLAN ID , fixed to 0 (but can c 06/21/2022 09:13 AM Actions
524 IEC 61850 User Feedback Task Force Support 5 IOP_2017/7 Closed Normal

1-Aug

The use of the Simulation bit in the R-GOOSE Payload is not clearly defined. It refers only to 8-1 which currently only specifie 06/21/2022 09:13 AM Actions
520 IEC 61850 User Feedback Task Force Support 1 IOP_2017/1 Closed Normal IEC 61850-6 leaves the definition of the meaning of the authentication options to the SCSM. However, neither 8-1 nor IEC 62351-6 06/21/2022 09:13 AM Actions
518 IEC 61850 User Feedback Task Force Support 34 IOP_2015 Closed Normal Does the SVID character have to be specifically mentioned to be within 10-34 characters? Some of the vendors have implemented th 06/21/2022 09:12 AM Actions
517 IEC 61850 User Feedback Task Force Support 33 IOP_2015 Closed Normal IEC 61850-9-3 slaves can by design lock themselves to IEEE C37.238 (Power Profile) masters. This is intended behavior, since IEC 06/21/2022 09:12 AM Actions
516 IEC 61850 User Feedback Task Force Support 32 IOP_2015 Closed Normal Buffered reporting testing – anomaly with resynch (write of entryId failed, but buffered reports still sent). Because of indexe 06/21/2022 09:12 AM Actions
515 IEC 61850 User Feedback Task Force Support 31 IOP_2015 Closed Normal These test cases assume that a server will send a negative response to an operate to the same value. Some servers will accept th 06/21/2022 09:12 AM Actions
514 IEC 61850 User Feedback Task Force Support 29 IOP_2015 Closed Normal Priority of error checking in controls – i.e. position-reached instead of Blocked-by-switching-hierarchy. The order of checks i 06/21/2022 09:12 AM Actions
512 IEC 61850 User Feedback Task Force Support 27 IOP_2015 Closed Normal

90-4

Testing unconfigured VLAN, there is a question of how VLAN tags (e.g. 20) should be handled by the HSR ring. However, what sho 06/21/2022 09:12 AM Actions
511 IEC 61850 User Feedback Task Force Support 26 IOP_2015 Closed Normal

2-Sep

The Quality bits alignment in 9-2LE seems different from 8-1 quality bits with ASN.1. So it caused confusion that which bit shou 06/21/2022 09:12 AM Actions
510 IEC 61850 User Feedback Task Force Support 25 IOP_2015 Closed Normal

IEC 61850-7-4

For the latest TISSUE 1361 for Ed2.0 (statement in the attachment), there are two things to be clarified:1. The statement: Swit 06/21/2022 09:12 AM Actions
509 IEC 61850 User Feedback Task Force Support 24 IOP_2015 Closed Normal

IEC 61850-7-2

1. Report Control Block is disabled and four events (four reports) are generated2. Client sends MMS Write RptEna=true to the BR 06/21/2022 09:12 AM Actions
508 IEC 61850 User Feedback Task Force Support 23 IOP_2015 Closed Normal

IEC 61850-7-2

RptID attribute of a ReportControl section in SCL is optional, as stated in IEC 61850-6. IEC 61850-8-1 states to send RCB objec 06/21/2022 09:12 AM Actions