# Project Tracker ID Source Status Priority Standard(s) Subject Updated
585 IEC 61850 User Feedback Task Force Feature 1337 IOP_2019 Closed Normal

IEC 61850-6

SCT unable to configure the device to communicate on multiple subnets due to having a single AP (with all Eth. Ports) 07/05/2022 08:24 AM Actions
586 IEC 61850 User Feedback Task Force Feature 1340 IOP_2019 Closed Normal

IEC 61850-6

Client application cannot connect to IED that are having issue with format of AP-Title 07/05/2022 08:26 AM Actions
457 IEC 61850 User Feedback Task Force Feature 14 IOP_2013 Closed Normal

IEC 61850-6

A SCL file is created without maxAttributes attribute defined. What does it mean semantically it the attr. is missing? 02/11/2021 07:46 AM Actions
533 IEC 61850 User Feedback Task Force Support 14 IOP_2017/23 Closed Normal MSVID shall be unique. The integrated application SCD file allowed duplicate SVID’s for two merging units. 06/21/2022 09:13 AM Actions
499 IEC 61850 User Feedback Task Force Support 14 IOP_2015 Closed Normal

6

Issue 4 – Private section – namespace moved from SCL node to Private nodes ICT added the namespace within the privates instead o 06/21/2022 09:12 AM Actions
423 IEC 61850 User Feedback Task Force Support 14 ENTSO-E Closed Normal Conformance test for SICS. 02/11/2021 07:47 AM Actions
587 IEC 61850 User Feedback Task Force Feature 1404 IOP_2019 Closed Normal

IEC 61850-6

LNodeTypes and DOTypes not used in the IED section - is it allowed to keep them in DataTypeTemplate section? 02/11/2021 07:01 AM Actions
458 IEC 61850 User Feedback Task Force Bug 15 IOP_2013 Closed High

IEC 61850-6

ICD issue when cBName="fix" but not all the RCBs has been declared 02/11/2021 06:15 AM Actions
534 IEC 61850 User Feedback Task Force Feature 15 IOP_2017/24 Closed Normal

IEC 61850-6, IEC 61850-7-2

A GCB or MSVCB can only have one single control block address entry in the whole communication section 06/21/2022 09:24 AM Actions
500 IEC 61850 User Feedback Task Force Support 15 IOP_2015 Closed Normal

6

2.2. BufMod is optional for ReportControl. No default value provided by the schema. SCT is interpreting as unbuffered only. Com 06/21/2022 09:12 AM Actions
424 IEC 61850 User Feedback Task Force Support 15 ENTSO-E Closed Normal

6

Vendor Tools shall allow (vendor independant) Integration tools doing engineering based on ICD Files, thus allowing them to in 12/06/2022 09:01 AM Actions
588 IEC 61850 User Feedback Task Force Feature 1548 IOP_2019 Closed Normal

IEC 61850-6

More than one redundant PhysConn for ConnectedAP of IED AP and no redundant PhysConn on same AP 06/21/2022 09:28 AM Actions
459 IEC 61850 User Feedback Task Force Bug 16 IOP_2013 Closed High

IEC 61850-6

No mechanism in SCL to indicate if the SCT can define/delete/edit RCBs/ExtRefs 06/21/2022 09:00 AM Actions
535 IEC 61850 User Feedback Task Force Support 16 IOP_2017/25 Closed Normal

6

SCD file removed unconfigured GOOSE control block but did not remove the Connected AP section contained GSE information. 06/21/2022 09:13 AM Actions
501 IEC 61850 User Feedback Task Force Support 16 IOP_2015 Closed Normal

6

PAUL MYRDA: In SCL it is possible to define unbuffered report control blocks with indexed set to false but with max instances se 06/21/2022 09:12 AM Actions
425 IEC 61850 User Feedback Task Force Support 16 ENTSO-E Closed Normal

IEC 61850-6

Restrictions in the configuration to be described in the ICD Service section 02/11/2021 07:44 AM Actions
593 IEC 61850 User Feedback Task Force Feature 1601 IOP_2019 Closed Normal

IEC 61850-6

How to disable SV control blocks that are not in use? 06/21/2022 09:29 AM Actions
594 IEC 61850 User Feedback Task Force Feature 1642_01 IOP_2019 Closed Normal

IEC 61850-6

Reverse engineering of subscription is not possible when Server and ServerAt APs are connected to the same SubNetwork 06/21/2022 09:29 AM Actions
595 IEC 61850 User Feedback Task Force Feature 1642_04 IOP_2019 Closed Normal

IEC 61850-7-1

How does the SCT know whether to configure the LSVS.SvCBRef (if it is not configured)? 06/21/2022 09:29 AM Actions
536 IEC 61850 User Feedback Task Force Support 17 IOP_2017/26 Closed Normal SCT did not import GOOSE and 3 of the sampled value control blocks that existed in PMU ICD file. This caused validation failures 06/21/2022 09:13 AM Actions
502 IEC 61850 User Feedback Task Force Support 17 IOP_2015 Closed Normal

6

Issue 1: During import of SSD file SST/SCT is not able to recognize Busbar connection node. It is connectivity node and there i 06/21/2022 09:12 AM Actions
460 IEC 61850 User Feedback Task Force Support 17 IOP_2013 Closed Normal The usage of ClientLN in RptEna is optional. What does this mean. 61850-6 made this option for backward compatibility with ED.1. 06/21/2022 09:00 AM Actions
426 IEC 61850 User Feedback Task Force Support 17 ENTSO-E Closed Normal

IEC 61850-6

SCT and ICD Service section handling 02/11/2021 07:43 AM Actions
589 IEC 61850 User Feedback Task Force Feature 1700 IOP_2019 Closed Normal

IEC 61850-6

Usage of max of RptEnabled when indexed attribute is false and the relationship to RptEnabled 07/05/2022 08:28 AM Actions
596 IEC 61850 User Feedback Task Force Feature 1710 IOP_2019 Closed Normal An IED declares constraints that are not machine processable 02/11/2021 06:43 AM Actions