sRpN9 does not specify the expected access error by negative response on SetURCBValues

Added by Ursula Kramarczyk 3 months ago. Updated about 1 month ago.

Status:
Resolved
Priority:
Normal
Due date:
04/02/2024 (36 days late)
Discuss in Upcoming Meeting:
Yes
Clause Reference:
61850 Standard:
7-2, 8-1
Triggering Tissue:
Final Decision:
Updated Test Document:
Test Case ID:
sRpN9
Closed Reason:
--Not Set---
Triggering Tissue 2:
Triggering Tissue 3:

Description

Basing on IEC 61850-7-2 Annex E (new in amd1) the current expected result of SetURCBValues without reservation (step 4 and 5) is:
DUT sends SetURCBValues response-

Basing on IEC 61850-8-1 SetURCBValues mapping to MMS Write it is the case "an object for which the MMS Client does not have access privileges". Thus, the expected result:
DUT sends SetURCBValues response- with data access error “object-access-denied”