Project

General

Profile

Issues #6210

sSvs4 remove PIXIT entry Svs3

Added by Hua Qin over 1 year ago. Updated about 2 months ago.

Status:
Closed
Priority:
Normal
Due date:
02/21/2023
Discuss in Upcoming Meeting:
No
Clause Reference:
61850 Standard:
Triggering Tissue:
Final Decision:
Initial Test Document:
Updated Test Document:
Test Case ID:
Closed Reason:
Test Procedure Update
Triggering Tissue 2:
Triggering Tissue 3:

Description

PIXIT Svs3 gives user the option to say Y or N to support simulation mode for preferred rate and backwards compatible rates.
sSvs4 only tests the preferred rate.
It is suggested to update case sSvs4.

  • Need to specify that the DUT shall be configured with maximum preferred variant of all preferred variants and one lowest rate backwards compatible.
  • Specify SV1 is the maximum preferred variant and SV2 is the lowest backwards rate to make test case clear
  • Add steps or description in original steps to cover the test for lowest rate backwards compatible sample values
  • similar as sGos6, step 1 to 3 are mandatory while step 4-7 are optional depending on the PIXIT entry Svs3. Should we separate this test cases to two parts as what we do in test cases sGos6.

Files

Solution to redmine 6210 sSvs4.docx Solution to redmine 6210 sSvs4.docx 23.3 KB Richard Schimmel, 02/21/2023 07:53 AM

Also available in: Atom PDF