Issues #6188
sSBOns8 does not consider PIXIT Ct13
Due date:
12/13/2022
Discuss in Upcoming Meeting:
Yes
Clause Reference:
61850 Standard:
Triggering Tissue:
Final Decision:
Initial Test Document:
Updated Test Document:
Test Case ID:
sSBOns8
Closed Reason:
--Not Set---
Triggering Tissue 2:
Triggering Tissue 3:
Description
The test description considers that a cancel service using the service parameter origin.orCat = 1 succeeds.
However the PIXIT Ct13 allows a range check of the service parameters for any control service.
It should be out of scope of the test to fix the order of the test. A device can decide to
- first check the range of the service paremeters
- and then verify the coherency of them vs the configured control model
Or first verify the coherency (and in this particuliar case: ignore the coherency) and then verify the range of allowed value.
I recommend to remove orCat from the list of parmeters, or to use an orCat that is allowed by the device based on PIXIT Ct13.
Files