Issues #6188
sSBOns8 does not consider PIXIT Ct13
Description
The test description considers that a cancel service using the service parameter origin.orCat = 1 succeeds.
However the PIXIT Ct13 allows a range check of the service parameters for any control service.
It should be out of scope of the test to fix the order of the test. A device can decide to
- first check the range of the service paremeters
- and then verify the coherency of them vs the configured control model
Or first verify the coherency (and in this particuliar case: ignore the coherency) and then verify the range of allowed value.
I recommend to remove orCat from the list of parmeters, or to use an orCat that is allowed by the device based on PIXIT Ct13.
Files
Updated by IEC 61850 TPWG almost 2 years ago
- Due date set to 12/13/2022
- Status changed from New to In Progress
- Assignee changed from IEC 61850 TPWG to Richard Schimmel
Agree with proposal:
Remove the orCat check from sSBOns8
Updated by Richard Schimmel almost 2 years ago
- File Solution to redmine 6188 sSBOns8.docx Solution to redmine 6188 sSBOns8.docx added
- Initial Test Document set to Ed2Amd1 TP1.2
added solution
Updated by Herbert Falk almost 2 years ago
- Status changed from In Progress to Resolved
Reviewed proposed test procedure during TPWG meeting.
Updated by Richard Schimmel 9 months ago
- Status changed from Resolved to Closed
- Updated Test Document set to TP1.3