sSBOns8 does not consider PIXIT Ct13

Added by Thierry Dufaure over 1 year ago. Updated about 2 months ago.

Status:
Closed
Priority:
Normal
Due date:
12/13/2022
Discuss in Upcoming Meeting:
Yes
Clause Reference:
61850 Standard:
Triggering Tissue:
Final Decision:
Initial Test Document:
Updated Test Document:
Test Case ID:
sSBOns8
Closed Reason:
--Not Set---
Triggering Tissue 2:
Triggering Tissue 3:

Description

The test description considers that a cancel service using the service parameter origin.orCat = 1 succeeds.
However the PIXIT Ct13 allows a range check of the service parameters for any control service.
It should be out of scope of the test to fix the order of the test. A device can decide to
- first check the range of the service paremeters
- and then verify the coherency of them vs the configured control model

Or first verify the coherency (and in this particuliar case: ignore the coherency) and then verify the range of allowed value.

I recommend to remove orCat from the list of parmeters, or to use an orCat that is allowed by the device based on PIXIT Ct13.


Files

#1

Updated by IEC 61850 TPWG over 1 year ago

  • Due date set to 12/13/2022
  • Status changed from New to In Progress
  • Assignee changed from IEC 61850 TPWG to Richard Schimmel

Agree with proposal:

Remove the orCat check from sSBOns8

#2

Updated by Richard Schimmel over 1 year ago

added solution

#3

Updated by Thierry Dufaure over 1 year ago

I agree with Richard proposal from Nov, 29.

#4

Updated by Herbert Falk over 1 year ago

  • Status changed from In Progress to Resolved

Reviewed proposed test procedure during TPWG meeting.

#5

Updated by Richard Schimmel about 2 months ago

  • Status changed from Resolved to Closed
  • Updated Test Document set to TP1.3