Issues #6188
sSBOns8 does not consider PIXIT Ct13
Description
The test description considers that a cancel service using the service parameter origin.orCat = 1 succeeds.
However the PIXIT Ct13 allows a range check of the service parameters for any control service.
It should be out of scope of the test to fix the order of the test. A device can decide to
- first check the range of the service paremeters
- and then verify the coherency of them vs the configured control model
Or first verify the coherency (and in this particuliar case: ignore the coherency) and then verify the range of allowed value.
I recommend to remove orCat from the list of parmeters, or to use an orCat that is allowed by the device based on PIXIT Ct13.
Files
Updated by IEC 61850 TPWG 6 months ago
- Due date set to 12/13/2022
- Status changed from New to In Progress
- Assignee changed from IEC 61850 TPWG to Richard Schimmel
Agree with proposal:
Remove the orCat check from sSBOns8
Updated by Richard Schimmel 6 months ago
- File Solution to redmine 6188 sSBOns8.docx Solution to redmine 6188 sSBOns8.docx added
- Initial Test Document set to Ed2Amd1 TP1.2
added solution
Updated by Herbert Falk 6 months ago
- Status changed from In Progress to Resolved
Reviewed proposed test procedure during TPWG meeting.