Feature #590
ICT fails to check validity of the SCD file regarding the IED constraints
0%
CBL to create a tissue to modify part 6 adding a statement about ICT having to check the validity of the SCD file regarding the IED constraints. We will need a SICS statement to test.
Device should reject config rather than serving part
IEC 61850-6
Description
Client/server test.
The data model uploaded in the Client from the SCD file (v7) shows 32 Buffered Report CB (brcbA01=>16 and brcbB01=>16). While trying to enable the BRCB “brcbA12”, we got an error response (object non existent).
In fact, this report brcbA12 doesn’t exist in the IED. It seems that the SCD, while instancing the RCB, exceeds the IED capabilities :
Extract from ICD file :
<ReportControl name="brcbA" confRev="0" buffered="true" desc="System Logical Device Report Control Block"> (…) <RptEnabled max="8"/>
Extract from SCD file
<ReportControl name="brcbA" confRev="60000" rptID="L2_PU_GE_P443_Meas" buffered="true" desc="System Logical Device Report Control Block" (…) <RptEnabled max="16">
Files
Proposal descriptions
Editor of Part 6 to create related TISSUE.