ICT fails to check validity of the SCD file regarding the IED constraints

Added by Herbert Falk about 3 years ago. Updated 5 months ago.

Status:
Resolved
Priority:
Normal
Assignee:
-
Category:
Implementation - improve conformance testing
Start date:
Due date:
% Done:

0%

Estimated time:
ID:
1800
Source:
IOP_2019
TF Unique ID:
1800 # IOP_2019
WG10 Proposal:

CBL to create a tissue to modify part 6 adding a statement about ICT having to check the validity of the SCD file regarding the IED constraints. We will need a SICS statement to test.

Estimated Completion:
20-Oct
Discuss in Upcoming Meeting:
No
To discuss in WG10:
No
Short Proposal:

Device should reject config rather than serving part

Standard(s):

IEC 61850-6

Needs More Information:
Yes
Assigned TF:

Description

Client/server test.
The data model uploaded in the Client from the SCD file (v7) shows 32 Buffered Report CB (brcbA01=>16 and brcbB01=>16). While trying to enable the BRCB “brcbA12”, we got an error response (object non existent).
In fact, this report brcbA12 doesn’t exist in the IED. It seems that the SCD, while instancing the RCB, exceeds the IED capabilities :
Extract from ICD file :
<ReportControl name="brcbA" confRev="0" buffered="true" desc="System Logical Device Report Control Block"> (…) <RptEnabled max="8"/>

Extract from SCD file
<ReportControl name="brcbA" confRev="60000" rptID="L2_PU_GE_P443_Meas" buffered="true" desc="System Logical Device Report Control Block" (…) <RptEnabled max="16">


Files

tissue 1893_V2.docx tissue 1893_V2.docx 29.2 KB Camille Bloch, 11/07/2023 08:22 AM

Proposal descriptions

Editor of Part 6 to create related TISSUE.


Related issues

Related to IEC 61850 User Feedback Task Force - Feature #591: A reservation could not be made via SCL for an IED’s report due to the lack of a ConnectedAP associated with the client’s APClosed

Actions
#1

Updated by Vladan Cvejic about 3 years ago

  • Subject changed from Client/server test. The data model uploaded in the Client from the SCD file (v7) shows 32 Buffered Report CB (brcbA01=>16 and br to ICT fails to check validity of the SCD file regarding the IED constraints
  • Status changed from New to In Progress
  • Standard(s) changed from 6 to IEC 61850-6
  • Discuss in Upcoming Meeting set to No

Checking done.

#2

Updated by Carlos Rodriguez del Castillo almost 2 years ago

  • Discuss in Upcoming Meeting changed from No to Yes
#3

Updated by Vladan Cvejic over 1 year ago

  • Discuss in Upcoming Meeting changed from Yes to No
  • Proposal descriptions updated (diff)
  • To discuss in WG10 set to No
#4

Updated by Vladan Cvejic over 1 year ago

  • Related to Feature #591: A reservation could not be made via SCL for an IED’s report due to the lack of a ConnectedAP associated with the client’s AP added
#5

Updated by Vladan Cvejic 5 months ago

  • Discuss in Upcoming Meeting changed from No to Yes
  • Needs More Information set to Yes
#7

Updated by Camille Bloch 5 months ago

  • File tissue 1893_V1.docx added
#8

Updated by Vladan Cvejic 5 months ago

  • Status changed from In Progress to Resolved
  • Discuss in Upcoming Meeting changed from Yes to No
#9

Updated by Camille Bloch 5 months ago

  • File deleted (tissue 1893_V1.docx)

Also available in: Atom PDF