Feature #5088
Clarifications on the local/remote concept 8/8
Added by Carlos Rodriguez del Castillo about 3 years ago.
Updated over 1 year ago.
Category:
Standard clarification required
Due date:
01/20/2022 (over 2 years late)
Discuss in Upcoming Meeting:
No
Needs More Information:
No
Description
Annex B, Table B.1 states that "Manual Control at switch (process)" was always allowed. Isn't it the status of a control switch modelled as XCBR.LocKey="true" which releases the manual control at the switchgear? As long as this control switch is not activated, manual control is not possible. To prevent from switchgear controls other than local during this time, as long as XCBR.LocKey="true", no control issued by the IED is accepted.
- Due date set to 01/20/2022
- Related to Feature #5081: Clarifications on the local/remote concept 1/8 added
- Status changed from New to In Progress
- Status changed from In Progress to Resolved
- Discuss in Upcoming Meeting changed from Yes to No
Proposed clarification:
In part 7-4 "Manual Control at switch (process) is always allowed" means a mechanical action, independent of the IED status.
Part 7-4 states that if XCBR.LocKey="true", then commands received via IEC 61850 control services will be blocked.
to add:
If XCBR.LocKey="true", then the IED may process control requests received directly by the IED, e.g. from the IED front panel HMI or push-buttons wired directly to the IED. There may be proprietary settings to enable or disable this feature.
- Assignee set to Tom Berry
- Standard(s) changed from IEC 61850-7-4 Ed2.1 to IEC 61850-7-4 Ed2.1 ,7-5
- Needs More Information set to No
- Discuss in Upcoming Meeting changed from No to Yes
- Discuss in Upcoming Meeting changed from Yes to No