Project

General

Profile

Feature #5088

Clarifications on the local/remote concept 8/8

Added by Carlos Rodriguez del Castillo about 3 years ago. Updated over 1 year ago.

Status:
Resolved
Priority:
Normal
Assignee:
Category:
Standard clarification required
Start date:
09/20/2021
Due date:
01/20/2022 (over 2 years late)
% Done:

0%

Estimated time:
ID:
12
Source:
MH
TF Unique ID:
12 # MH
WG10 Proposal:
Estimated Completion:
Discuss in Upcoming Meeting:
No
To discuss in WG10:
No
Short Proposal:
Standard(s):

IEC 61850-7-4 Ed2.1 ,7-5

Needs More Information:
No
Assigned TF:

Description

Annex B, Table B.1 states that "Manual Control at switch (process)" was always allowed. Isn't it the status of a control switch modelled as XCBR.LocKey="true" which releases the manual control at the switchgear? As long as this control switch is not activated, manual control is not possible. To prevent from switchgear controls other than local during this time, as long as XCBR.LocKey="true", no control issued by the IED is accepted.


Related issues

Related to IEC 61850 User Feedback Task Force - Feature #5081: Clarifications on the local/remote concept 1/8ResolvedTom Berry09/20/2021

Actions
Copied to 61850-7-5 and 61850-7-500 - IEC61850-7-5 #6394: Clarifications on the local/remote concept 8/8In Progress09/20/202101/20/2022

Actions

Also available in: Atom PDF