Project

General

Profile

IEC61850-7-5 #6394

Clarifications on the local/remote concept 8/8

Added by Vladan Cvejic 11 months ago. Updated 8 months ago.

Status:
In Progress
Priority:
Normal
Assignee:
-
Start date:
09/20/2021
Due date:
01/20/2022 (over 2 years late)
% Done:

0%

Source:
Category:
Not yet categorized
TF 7-5 Project document:
IEC 61850-7-5
Related TISSUE:

Description

Annex B, Table B.1 states that "Manual Control at switch (process)" was always allowed. Isn't it the status of a control switch modelled as XCBR.LocKey="true" which releases the manual control at the switchgear? As long as this control switch is not activated, manual control is not possible. To prevent from switchgear controls other than local during this time, as long as XCBR.LocKey="true", no control issued by the IED is accepted.


Related issues

Copied from IEC 61850 User Feedback Task Force - Feature #5088: Clarifications on the local/remote concept 8/8ResolvedTom Berry09/20/202101/20/2022

Actions
#1

Updated by Vladan Cvejic 11 months ago

  • Copied from Feature #5088: Clarifications on the local/remote concept 8/8 added
#2

Updated by Keith Gray 8 months ago

  • Status changed from New to In Progress
  • TF 7-5 Project document IEC 61850-7-5 added

Also available in: Atom PDF