Project

General

Profile

Feature #5088

Clarifications on the local/remote concept 8/8

Added by Carlos Rodriguez del Castillo about 3 years ago. Updated over 1 year ago.

Status:
Resolved
Priority:
Normal
Assignee:
Category:
Standard clarification required
Start date:
09/20/2021
Due date:
01/20/2022 (over 2 years late)
% Done:

0%

Estimated time:
ID:
12
Source:
MH
TF Unique ID:
12 # MH
WG10 Proposal:
Estimated Completion:
Discuss in Upcoming Meeting:
No
To discuss in WG10:
No
Short Proposal:
Standard(s):

IEC 61850-7-4 Ed2.1 ,7-5

Needs More Information:
No
Assigned TF:

Description

Annex B, Table B.1 states that "Manual Control at switch (process)" was always allowed. Isn't it the status of a control switch modelled as XCBR.LocKey="true" which releases the manual control at the switchgear? As long as this control switch is not activated, manual control is not possible. To prevent from switchgear controls other than local during this time, as long as XCBR.LocKey="true", no control issued by the IED is accepted.


Related issues

Related to IEC 61850 User Feedback Task Force - Feature #5081: Clarifications on the local/remote concept 1/8ResolvedTom Berry09/20/2021

Actions
Copied to 61850-7-5 and 61850-7-500 - IEC61850-7-5 #6394: Clarifications on the local/remote concept 8/8In Progress09/20/202101/20/2022

Actions
#1

Updated by Carlos Rodriguez del Castillo about 3 years ago

  • Due date set to 01/20/2022
#2

Updated by Vladan Cvejic over 2 years ago

  • Related to Feature #5081: Clarifications on the local/remote concept 1/8 added
#3

Updated by Vladan Cvejic over 2 years ago

  • Status changed from New to In Progress
#4

Updated by Vladan Cvejic over 2 years ago

  • Status changed from In Progress to Resolved
  • Discuss in Upcoming Meeting changed from Yes to No
#5

Updated by Tom Berry over 2 years ago

Proposed clarification:
In part 7-4 "Manual Control at switch (process) is always allowed" means a mechanical action, independent of the IED status.

Part 7-4 states that if XCBR.LocKey="true", then commands received via IEC 61850 control services will be blocked.
to add:
If XCBR.LocKey="true", then the IED may process control requests received directly by the IED, e.g. from the IED front panel HMI or push-buttons wired directly to the IED. There may be proprietary settings to enable or disable this feature.

#6

Updated by Carlos Rodriguez del Castillo over 2 years ago

  • Assignee set to Tom Berry
#7

Updated by Tom Berry over 2 years ago

  • Standard(s) changed from IEC 61850-7-4 Ed2.1 to IEC 61850-7-4 Ed2.1 ,7-5
#8

Updated by Carlos Rodriguez del Castillo over 1 year ago

  • Needs More Information set to No
#9

Updated by Carlos Rodriguez del Castillo over 1 year ago

  • Discuss in Upcoming Meeting changed from No to Yes
#10

Updated by Carlos Rodriguez del Castillo over 1 year ago

  • Discuss in Upcoming Meeting changed from Yes to No
#11

Updated by Vladan Cvejic over 1 year ago

Also available in: Atom PDF