Feature #5088

Clarifications on the local/remote concept 8/8

Added by Carlos Rodriguez del Castillo about 1 year ago. Updated 8 months ago.

Status:
Resolved
Priority:
Normal
Assignee:
Category:
Standard clarification required
Start date:
09/20/2021
Due date:
01/20/2022 (about 8 months late)
% Done:

0%

Estimated time:
ID:
12
Source:
MH
TF Unique ID:
12 # MH
WG10 Proposal:
Estimated Completion:
Discuss in Upcoming Meeting:
No
To discuss in WG10:
No
Short Proposal:
Standard(s):

IEC 61850-7-4 Ed2.1 ,7-5


Description

Annex B, Table B.1 states that "Manual Control at switch (process)" was always allowed. Isn't it the status of a control switch modelled as XCBR.LocKey="true" which releases the manual control at the switchgear? As long as this control switch is not activated, manual control is not possible. To prevent from switchgear controls other than local during this time, as long as XCBR.LocKey="true", no control issued by the IED is accepted.


Related issues

Related to IEC 61850 User Feedback Task Force - Feature #5081: Clarifications on the local/remote concept 1/8ResolvedTom Berry09/20/2021

Actions
#1

Updated by Carlos Rodriguez del Castillo about 1 year ago

  • Due date set to 01/20/2022
#2

Updated by Vladan Cvejic 8 months ago

  • Related to Feature #5081: Clarifications on the local/remote concept 1/8 added
#3

Updated by Vladan Cvejic 8 months ago

  • Status changed from New to In Progress
#4

Updated by Vladan Cvejic 8 months ago

  • Status changed from In Progress to Resolved
  • Discuss in Upcoming Meeting changed from Yes to No
#5

Updated by Tom Berry 8 months ago

Proposed clarification:
In part 7-4 "Manual Control at switch (process) is always allowed" means a mechanical action, independent of the IED status.

Part 7-4 states that if XCBR.LocKey="true", then commands received via IEC 61850 control services will be blocked.
to add:
If XCBR.LocKey="true", then the IED may process control requests received directly by the IED, e.g. from the IED front panel HMI or push-buttons wired directly to the IED. There may be proprietary settings to enable or disable this feature.

#6

Updated by Carlos Rodriguez del Castillo 8 months ago

  • Assignee set to Tom Berry
#7

Updated by Tom Berry 8 months ago

  • Standard(s) changed from IEC 61850-7-4 Ed2.1 to IEC 61850-7-4 Ed2.1 ,7-5