Feature #5083

Clarifications on the local/remote concept 3/8

Added by Carlos Rodriguez del Castillo about 3 years ago. Updated over 1 year ago.

Status:
Resolved
Priority:
Normal
Assignee:
Category:
Standard clarification required
Start date:
09/20/2021
Due date:
03/20/2022 (over 2 years late)
% Done:

0%

Estimated time:
ID:
7
Source:
MH
TF Unique ID:
7 # MH
WG10 Proposal:
Estimated Completion:
Discuss in Upcoming Meeting:
No
To discuss in WG10:
No
Short Proposal:

Include a statement

Standard(s):

IEC 61850-7-1 Ed2.1,7-5

Needs More Information:
No
Assigned TF:

Description

Add a statement about the use of XCBR.Loc (and similar LN classes). Assume XCBR.Loc="true". Will protection trips and switchgear controls by GAPC be rejected?


Proposal descriptions

Not affected by Loc DO:
- Protection trips are not affected by Loc data object.
- GAPC.Op (will go through) --> PTRC.Tr (to trip) --> XCBR

Otherwise, they are affected by Loc DO (control model)
- GAPC SPC/DPC/APC controllable objects will be affected by Loc data object.

The proposal is to include a statement about this behaviour in 7-1. There is a section about local/remote in 7-1, maybe it is the good place for that.


Related issues

Related to IEC 61850 User Feedback Task Force - Feature #5081: Clarifications on the local/remote concept 1/8ResolvedTom Berry09/20/2021

Actions
Copied to 61850-7-5 and 61850-7-500 - IEC61850-7-5 #6389: Clarifications on the local/remote concept 3/8In Progress09/20/202103/20/2022