Project

General

Profile

Feature #5084

Clarifications on the local/remote concept 4/8

Added by Carlos Rodriguez del Castillo over 1 year ago. Updated 19 days ago.

Status:
Resolved
Priority:
Normal
Assignee:
Category:
Standard clarification required
Start date:
09/20/2021
Due date:
% Done:

0%

Estimated time:
ID:
8
Source:
MH
TF Unique ID:
8 # MH
WG10 Proposal:
Estimated Completion:
Discuss in Upcoming Meeting:
Yes
To discuss in WG10:
No
Short Proposal:
Standard(s):

IEC 61850-7-1 Ed2.1,7-5

Needs More Information:
No

Description

Add a statement about the dependency of LD contained LN.LocSta from LD/LLN0.LocSta . Part 7-1 clause 6.4.2.1, Figure 14 states "for complete LD". Is the statement in the figure applicable for 'MtlLev' only or for both 'MltLev' and 'LocSta'?


Related issues

Related to IEC 61850 User Feedback Task Force - Feature #5081: Clarifications on the local/remote concept 1/8ResolvedTom Berry09/20/2021

Actions
#1

Updated by Vladan Cvejic over 1 year ago

  • Related to Feature #5083: Clarifications on the local/remote concept 3/8 added
#2

Updated by Vladan Cvejic over 1 year ago

  • Related to Feature #5081: Clarifications on the local/remote concept 1/8 added
#3

Updated by Vladan Cvejic over 1 year ago

  • Related to deleted (Feature #5083: Clarifications on the local/remote concept 3/8)
#4

Updated by Vladan Cvejic over 1 year ago

  • Status changed from New to In Progress
#5

Updated by Vladan Cvejic over 1 year ago

  • Status changed from In Progress to Resolved
  • Discuss in Upcoming Meeting changed from Yes to No
#6

Updated by Tom Berry over 1 year ago

Draft proposal
When there are nested logical devices, the control service checks for local/remote should be similar to the checks for Mod/Beh.

When a control request is received at a Logical Node, the checks should take into account the status of the Loc, LocSta, MltLev data objects of the logical node, and also the Loc, LocSta, MltLev data objects of the LLN0 for all containing logical devices.
In the case of different values, "Loc=true", "LocSta=true", "MltLev=False" are dominant.

#7

Updated by Carlos Rodriguez del Castillo over 1 year ago

  • Assignee set to Tom Berry
#8

Updated by Tom Berry over 1 year ago

  • Standard(s) changed from IEC 61850-7-1 Ed2.1 to IEC 61850-7-1 Ed2.1,7-5
#9

Updated by Carlos Rodriguez del Castillo 19 days ago

  • Needs More Information set to No
#10

Updated by Carlos Rodriguez del Castillo 19 days ago

  • Discuss in Upcoming Meeting changed from No to Yes

Also available in: Atom PDF