Feature #5084
Clarifications on the local/remote concept 4/8
0%
IEC 61850-7-1 Ed2.1,7-5
Description
Add a statement about the dependency of LD contained LN.LocSta from LD/LLN0.LocSta . Part 7-1 clause 6.4.2.1, Figure 14 states "for complete LD". Is the statement in the figure applicable for 'MtlLev' only or for both 'MltLev' and 'LocSta'?
Related issues
Updated by Vladan Cvejic over 1 year ago
- Related to Feature #5083: Clarifications on the local/remote concept 3/8 added
Updated by Vladan Cvejic over 1 year ago
- Related to Feature #5081: Clarifications on the local/remote concept 1/8 added
Updated by Vladan Cvejic over 1 year ago
- Related to deleted (Feature #5083: Clarifications on the local/remote concept 3/8)
Updated by Vladan Cvejic over 1 year ago
- Status changed from In Progress to Resolved
- Discuss in Upcoming Meeting changed from Yes to No
Updated by Tom Berry over 1 year ago
Draft proposal
When there are nested logical devices, the control service checks for local/remote should be similar to the checks for Mod/Beh.
When a control request is received at a Logical Node, the checks should take into account the status of the Loc, LocSta, MltLev data objects of the logical node, and also the Loc, LocSta, MltLev data objects of the LLN0 for all containing logical devices.
In the case of different values, "Loc=true", "LocSta=true", "MltLev=False" are dominant.
Updated by Tom Berry over 1 year ago
- Standard(s) changed from IEC 61850-7-1 Ed2.1 to IEC 61850-7-1 Ed2.1,7-5
Updated by Carlos Rodriguez del Castillo 19 days ago
- Discuss in Upcoming Meeting changed from No to Yes