Project

General

Profile

Feature #5082

Clarifications on the local/remote concept 2/8

Added by Carlos Rodriguez del Castillo over 2 years ago. Updated 11 months ago.

Status:
Resolved
Priority:
Normal
Assignee:
Category:
Standard clarification required
Start date:
09/20/2021
Due date:
01/20/2022 (over 2 years late)
% Done:

0%

Estimated time:
ID:
6
Source:
MH
TF Unique ID:
6 # MH
WG10 Proposal:
Estimated Completion:
Discuss in Upcoming Meeting:
No
To discuss in WG10:
No
Short Proposal:

Should we state that "automatic-bay/station/remote" orCat would not be blocked by L/R concept?

Standard(s):

IEC 61850-7-4,7-5

Needs More Information:
No
Assigned TF:

Description

Add a statement about the intention of the L/R concept. Specify whether the L/R concept is applicable for operator controls exclusively, not for switchgear controls in general.
Assume LD/LLN0.Loc="false". Will a switchgear control by GAPC (orCat="automatic-bay") be executed?


Proposal descriptions

We think the solution should be in IEC 61850-7-4 Annex B table with a clarification with some use cases.
Use cases could be created in 7-500.


Related issues

Related to IEC 61850 User Feedback Task Force - Feature #5081: Clarifications on the local/remote concept 1/8ResolvedTom Berry09/20/2021

Actions
Copied to 61850-7-5 and 61850-7-500 - IEC61850-7-5 #6388: Clarifications on the local/remote concept 2/8In Progress09/20/202101/20/2022

Actions

Also available in: Atom PDF