Feature #5082

Clarifications on the local/remote concept 2/8

Added by Carlos Rodriguez del Castillo about 3 years ago. Updated over 1 year ago.

Status:
Resolved
Priority:
Normal
Assignee:
Category:
Standard clarification required
Start date:
09/20/2021
Due date:
01/20/2022 (over 2 years late)
% Done:

0%

Estimated time:
ID:
6
Source:
MH
TF Unique ID:
6 # MH
WG10 Proposal:
Estimated Completion:
Discuss in Upcoming Meeting:
No
To discuss in WG10:
No
Short Proposal:

Should we state that "automatic-bay/station/remote" orCat would not be blocked by L/R concept?

Standard(s):

IEC 61850-7-4,7-5

Needs More Information:
No
Assigned TF:

Description

Add a statement about the intention of the L/R concept. Specify whether the L/R concept is applicable for operator controls exclusively, not for switchgear controls in general.
Assume LD/LLN0.Loc="false". Will a switchgear control by GAPC (orCat="automatic-bay") be executed?


Proposal descriptions

We think the solution should be in IEC 61850-7-4 Annex B table with a clarification with some use cases.
Use cases could be created in 7-500.


Related issues

Related to IEC 61850 User Feedback Task Force - Feature #5081: Clarifications on the local/remote concept 1/8ResolvedTom Berry09/20/2021