Feature #5082

Clarifications on the local/remote concept 2/8

Added by Carlos Rodriguez del Castillo over 2 years ago. Updated 10 months ago.

Status:
Resolved
Priority:
Normal
Assignee:
Category:
Standard clarification required
Start date:
09/20/2021
Due date:
01/20/2022 (over 2 years late)
% Done:

0%

Estimated time:
ID:
6
Source:
MH
TF Unique ID:
6 # MH
WG10 Proposal:
Estimated Completion:
Discuss in Upcoming Meeting:
No
To discuss in WG10:
No
Short Proposal:

Should we state that "automatic-bay/station/remote" orCat would not be blocked by L/R concept?

Standard(s):

IEC 61850-7-4,7-5

Needs More Information:
No
Assigned TF:

Description

Add a statement about the intention of the L/R concept. Specify whether the L/R concept is applicable for operator controls exclusively, not for switchgear controls in general.
Assume LD/LLN0.Loc="false". Will a switchgear control by GAPC (orCat="automatic-bay") be executed?


Proposal descriptions

We think the solution should be in IEC 61850-7-4 Annex B table with a clarification with some use cases.
Use cases could be created in 7-500.


Related issues

Related to IEC 61850 User Feedback Task Force - Feature #5081: Clarifications on the local/remote concept 1/8ResolvedTom Berry09/20/2021

Actions
Copied to 61850-7-5 and 61850-7-500 - IEC61850-7-5 #6388: Clarifications on the local/remote concept 2/8In Progress09/20/202101/20/2022

Actions
#1

Updated by Carlos Rodriguez del Castillo about 2 years ago

  • Status changed from New to In Progress
  • Proposal descriptions updated (diff)
  • Short Proposal set to Should we state that "automatic-bay/station/remote" orCat would not be blocked by L/R concept?
  • Standard(s) changed from IEC 61850-7-1 Ed2.1 to IEC 61850-7-4

Situation:
- We have an IED running some automation process with a GAPC instance
- The GAPC could control a breaker or switch
- If the IED is in remote, does GAPC automatic control (orCat=automatic-bay) be executed?
According to IEC 61850-7-4 Annex B, in order to make it executable, MltLev should be implemented and set to True.
But, also, should an IED in remote state block automatic controls? Today it is an implementation issue in IEDs.
Should we state that "automatic-bay" orCat would not be blocked by L/R concept? There are three orCat values (automatic-bay, automatic-station, automatic-remote). orCat is also used to provide the reason in the return information.

#2

Updated by Vladan Cvejic about 2 years ago

  • Related to Feature #5081: Clarifications on the local/remote concept 1/8 added
#3

Updated by Vladan Cvejic about 2 years ago

  • Status changed from In Progress to Resolved
  • Discuss in Upcoming Meeting changed from Yes to No
#4

Updated by Tom Berry about 2 years ago

Proposed clarification
Normally automation commands should be processed in exactly the same way as operator commands, which includes the local/remote status, interlocks or command blocking.
Some customers may want a different behaviour. This should be defined in the PIXIT or with extension configuration settings.

Proposal: extension optional configuration setting for LLN0 and/or CSWI

LocBlkAut SPG enable local mode to block automation controls
If the value is true then for controls with orCat values "automatic-bay/automatic-station/automatic-remote" are blocked if Loc status is true.
If the value is false then for controls with orCat values "automatic-bay/automatic-station/automatic-remote", the Loc status is ignored.
If the setting is not instantiated then for controls with orCat values "automatic-bay/automatic-station/automatic-remote", then the Loc status is applied in the same way as controls from an operator.

Alternative
LockBlkAutLev ENG defines which level of automation commands are blocked if this logical node or device is in local mode
Enumerated setting: 0=all-automatic-commands-allowed, 4=local-blocks-automatic-bay, 5=local-blocks-automatic-station, 6=local-blocks-automatic-remote

#5

Updated by Carlos Rodriguez del Castillo about 2 years ago

  • Assignee set to Tom Berry
#6

Updated by Tom Berry about 2 years ago

  • Standard(s) changed from IEC 61850-7-4 to IEC 61850-7-4,7-5
#7

Updated by Carlos Rodriguez del Castillo 11 months ago

  • Needs More Information set to No
#8

Updated by Carlos Rodriguez del Castillo 11 months ago

  • Discuss in Upcoming Meeting changed from No to Yes
#9

Updated by Carlos Rodriguez del Castillo 10 months ago

  • Discuss in Upcoming Meeting changed from Yes to No
#10

Updated by Vladan Cvejic 10 months ago