CIM Issues #749

There are a variety of issues with RegulatingControl. These include the following and must be addressed in CIM18

Added by Herbert Falk almost 2 years ago. Updated almost 2 years ago.

Status:
New
Priority:
Normal
Solution Version:
Breaking Change:
Yes
Breaking Change Description:
This is breaking
CIM Impacted Groups:
Requestor:
Standard(s):
Version:
Clause:
Sub-Clause:
Paragraph:
Table:
Origination Date:
Origination ID:
Originally Assigned To:

Description

There are a variety of issues with RegulatingControl. These include the following and must be addressed in CIM18:

There are multiple issues with the CIM control model:

1. Multiple RegulatingControls on the same controlled point as you describe. One reason to use multiple regulating controls is discrete vs continuous control that require different parameter settings. All RegulatingControls on the same power flow bus must then be enabled.

2. With multiple RegulatingControls they may have different target values (targetValue) which force the receiving tool to make a choice. If different tools make different choices then we have a problem. I have seen this in a few IGMs.

3. The control dead band (targetDeadband) is different for different type of devices which makes it difficult to use the same RegulatingControl, e.g. switched and tapped shunts.

4. A RegulatingControl is connected to the controlled power flow bus (TopologicalNode) via a Terminal. In a node breaker model it is common that the Terminal is at a Switch. It may then happen that the RegulatingControl becomes disconnected from the power flow bus as a consequence of switching while the controlling devices (subclasses of RequlatingCondEq) are still actively controlling. This has been observed to happen in several IGMs.

So the CIM voltage/reactive control model is broken and need a complete revision. For backwards compatibility we must keep the current in parallel with the revised.