Project

General

Profile

Issues #7101

sLog13 is LCB.LogRef always writable (SCL Services LogSettings has no attribute for LogRef)

Added by Richard Schimmel 15 days ago. Updated 14 days ago.

Status:
New
Priority:
Normal
Assignee:
-
Due date:
Discuss in Upcoming Meeting:
No
Clause Reference:
61850 Standard:
6
Triggering Tissue:
Final Decision:
Initial Test Document:
Updated Test Document:
Test Case ID:
sLog13
Closed Reason:
--Not Set---
Triggering Tissue 2:
Triggering Tissue 3:

Description

The SCL Services LogSettings do have dyn/conf/fix attributes for LCB.datSet-logEna - trgOps - intgPd. but not for LogRef !

The sLog13 requires to check if LCB.LogRef is writable or not. Part 8-1 table 75 indicates the MMS LCB.LogRef is "r/w".
It seems an SCL attribute is missing. We need clarification

Some proposals:
1) long term: add an SCL entry LogSetting logRef
2) short term: add an PIXIT entry to indicate logRef is writable or not
3) change logRef to readonly?