Support #675

Clarification of blocked mode

Added by Maud Merley almost 2 years ago. Updated over 1 year ago.

Status:
Resolved
Priority:
Normal
Assignee:
-
Category:
Standard clarification required
Start date:
05/21/2021
Due date:
11/21/2021 (about 16 months late)
% Done:

0%

Estimated time:
ID:
48
Source:
RTE
TF Unique ID:
48 # RTE
WG10 Proposal:
Estimated Completion:
Discuss in Upcoming Meeting:
No
To discuss in WG10:
No
Short Proposal:

Create an InterOp tissue in 7-4 ed2.1

Standard(s):

IEC 61850-7-4 Ed2.1

Needs More Information:

Description

IEC 61850-7-4 defines blocked mode as “No (wired) output data (digital by relays or analogue setpoints) will be issued to the process. ».
Does "no order is issued" means "no modification of contact of binary output", or "binary outup in idle state (define by configuration)"?

Proposal to discuss :
- the contact for transient outputs to assume its default position (open if normally open and closed if normally closed).
- the contact for non-transient outputs to remain in its state

#1

Updated by Carlos Rodriguez del Castillo almost 2 years ago

  • Discuss in Upcoming Meeting changed from No to Yes
#2

Updated by Carlos Rodriguez del Castillo over 1 year ago

  • Due date set to 11/21/2021
  • Category set to Standard clarification required
  • Status changed from New to Resolved
  • Discuss in Upcoming Meeting changed from Yes to No
  • Short Proposal set to Create an InterOp tissue in 7-4 ed2.1
  • Standard(s) set to IEC 61850-7-4 Ed2.1

2021-09-28:
- The original idea was not to trip the breaker when in test mode
- Agreee to create an InterOp tissue in 7-4 Ed2.1

#3

Updated by Carlos Rodriguez del Castillo over 1 year ago

M.H. to create the tissue

#4

Updated by Michael Haecker over 1 year ago

Done - Tissue #1793

#5

Updated by Carlos Rodriguez del Castillo over 1 year ago

  • ID set to 48
  • TF Unique ID set to 48 # RTE

TF Unique ID set