Support #675
Clarification of blocked mode
0%
Create an InterOp tissue in 7-4 ed2.1
IEC 61850-7-4 Ed2.1
Description
IEC 61850-7-4 defines blocked mode as “No (wired) output data (digital by relays or analogue setpoints) will be issued to the process. ».
Does "no order is issued" means "no modification of contact of binary output", or "binary outup in idle state (define by configuration)"?
Proposal to discuss :
- the contact for transient outputs to assume its default position (open if normally open and closed if normally closed).
- the contact for non-transient outputs to remain in its state
Updated by Carlos Rodriguez del Castillo over 3 years ago
- Discuss in Upcoming Meeting changed from No to Yes
Updated by Carlos Rodriguez del Castillo about 3 years ago
- Due date set to 11/21/2021
- Category set to Standard clarification required
- Status changed from New to Resolved
- Discuss in Upcoming Meeting changed from Yes to No
- Short Proposal set to Create an InterOp tissue in 7-4 ed2.1
- Standard(s) set to IEC 61850-7-4 Ed2.1
2021-09-28:
- The original idea was not to trip the breaker when in test mode
- Agreee to create an InterOp tissue in 7-4 Ed2.1
Updated by Michael Haecker about 3 years ago
Done - Tissue No 1793 (https://iec61850.tissue-db.com/tissue/1793)
Updated by Carlos Rodriguez del Castillo about 3 years ago
- ID set to 48
- TF Unique ID set to 48 # RTE
TF Unique ID set
Updated by Carlos Rodriguez del Castillo over 1 year ago
- Discuss in Upcoming Meeting changed from No to Yes
Updated by Carlos Rodriguez del Castillo over 1 year ago
The tissue is in red state, no intermediate 2.2 edition of 7-4, we will expect to have it included in Ed3.
Updated by Carlos Rodriguez del Castillo over 1 year ago
- Discuss in Upcoming Meeting changed from Yes to No
Updated by Vladan Cvejic about 1 year ago
- Discuss in Upcoming Meeting changed from Yes to No
Tissue 1793 is still under discussion.