Project

General

Profile

Improvement #672

Create DO indicating the source of synchronisation

Added by Maud Merley over 3 years ago. Updated about 1 year ago.

Status:
Resolved
Priority:
Normal
Assignee:
-
Category:
Standard extension required
Start date:
05/17/2021
Due date:
10/17/2021 (over 3 years late)
% Done:

0%

Estimated time:
ID:
46
Source:
RTE
TF Unique ID:
46 # RTE
WG10 Proposal:
Estimated Completion:
Discuss in Upcoming Meeting:
No
To discuss in WG10:
No
Short Proposal:
Standard(s):

TR IEC 61850-7-500

Needs More Information:
No
Assigned TF:
61850-7-500 Ed2

Description

Proposal to add in LTMS a DO indicating the current source of synchronisation of the IED. This should be done in a consistent way with SynSrcId added in the SV ADSU in 9-2 ed2.1.
Proposal: add new DO (> 64 bit ) to LTMS and MMXU.


Proposal descriptions

- For LTMS, 7-4 Ed2.1 already addresses the issue.
- For MMXU, it does not seem to be the best place to have the proposed new DO. Maybe the proxy TCTR or TVTR in the subscriber is the good place to have the DO indicating the time source of the sampled value stream the instance is connected to. Also LSVS could be a better place to have this information. To be discussed in WG10.
- Issue should be addressed by TF 7-500


Related issues

Copied to 61850-7-5 and 61850-7-500 - IEC61850-7-5 #6607: Create DO indicating the source of synchronisationNew05/17/202110/17/2021