Issues #6722

sGop10 PIXIT reference needed ?

Added by christian zehnder 2 months ago. Updated 7 days ago.

Status:
In Progress
Priority:
Normal
Due date:
05/28/2024 (Due in 19 days)
Discuss in Upcoming Meeting:
No
Clause Reference:
61850 Standard:
Triggering Tissue:
Final Decision:
Updated Test Document:
Test Case ID:
Closed Reason:
Test Procedure Update
Triggering Tissue 2:
Triggering Tissue 3:

Description

In TPCL Ed2.1 v1p2 sGop10 detail was missing as reported in Issue 5954. It was agreed to add the one from V1p1. sGop10 is mandatory and contains 2 steps to test FCDA and/or FCD according to PIXIT. There is no PIXIT reference.
If dataset are configurable both steps are "applicable" >mandatory. If fixed one seems ok.
PIXIT Gp8 is for edition 1 only. Shall we reference to this or create new one?
- If DS are fixed it seems only one step needs to be tested. Whatever is implemented. So FCDA is not mandatory (as its was in ED1)
- Do we need a PIXIT entry at all? If fixed tester cannot modify he can check what exists. If its configurable both steps are applicable. Is configurable IED allowed to support only FCDA or FCD? Then we need Pixit.

Background: Discussion what needs to be supported in a fixed server. Only FCDA seems ok. If not fixed they would be forced to implement FCD too.