Issues #6631
tTf1 (mustUnderstand) for the ICT test needs clarification
Description
Copied from #6622:
The test should be modified to test three scenarios.
1) An element has a mustUnderstand in the communication section of the IED being configured, but the IED being configured does not support it.
The ICT should reject the configuration of the IED and provide an error message.
2) An element has a mustUnderstand outside the scope of the IED being configured.
The ICT should import the file.
3) An element has a mustUnderstand element that is in another device but the SCD is configured for use in the IED being configured.
The ICT should reject the configuration of the IED and provide an error message.
Currently (in Ed2.1) mustUnderstand is only used for R-GOOSE and R-SV.
Files
Updated by IEC 61850 TPWG 10 months ago
- Due date set to 01/09/2024
- Status changed from New to In Progress
- Assignee set to Richard Schimmel
Accepted. Richard to propose test cases.
Possible standard clarification needed?