Project

General

Profile

Issues #6631

tTf1 (mustUnderstand) for the ICT test needs clarification

Added by Richard Schimmel 12 months ago. Updated 11 months ago.

Status:
Resolved
Priority:
Normal
Due date:
01/09/2024 (about 11 months late)
Discuss in Upcoming Meeting:
No
Clause Reference:
61850 Standard:
6
Triggering Tissue:
Final Decision:
Initial Test Document:
Updated Test Document:
Test Case ID:
tTf1
Closed Reason:
--Not Set---
Triggering Tissue 2:
Triggering Tissue 3:

Description

Copied from #6622:
The test should be modified to test three scenarios.
1) An element has a mustUnderstand in the communication section of the IED being configured, but the IED being configured does not support it.
The ICT should reject the configuration of the IED and provide an error message.
2) An element has a mustUnderstand outside the scope of the IED being configured.
The ICT should import the file.
3) An element has a mustUnderstand element that is in another device but the SCD is configured for use in the IED being configured.
The ICT should reject the configuration of the IED and provide an error message.

Currently (in Ed2.1) mustUnderstand is only used for R-GOOSE and R-SV.


Files

Solution to redmine 6631 tTf1.docx Solution to redmine 6631 tTf1.docx 24.2 KB Richard Schimmel, 01/09/2024 08:58 AM
#1

Updated by IEC 61850 TPWG 12 months ago

  • Due date set to 01/09/2024
  • Status changed from New to In Progress
  • Assignee set to Richard Schimmel

Accepted. Richard to propose test cases.

Possible standard clarification needed?

#3

Updated by IEC 61850 TPWG 11 months ago

  • Status changed from In Progress to Resolved

Also available in: Atom PDF