Issues #6489
Reducing the needed resources for time correlated subscribed GOOSE not used for ping-pong
Description
The tests include subscribing to time correlated GOOSE not used for ping-pong. The DUT is required to subscribe to 5*32 data = 160 data.
Since there is no benefit in subscribing to 160 different data, this is to propose to refer to the same dataset by each of the five GoCB. Then only 32 different GOOSE inputs are needed, as all the five GOOSE messages will publish the same data. There is no other effect to the performance to be awaited if 160 different GOOSE inputs are updated compared to updating five times the same 32 GOOSE inputs.
As not all devices provide hundreds of GOOSE inputs, this will free a couple of resources.
Files
Updated by Richard Schimmel over 1 year ago
The device under test only need to subscribe to one element per dataset/GoCB. In total only 7 elements need to be subscribed: 1 normal, 1 large and 5 time-correlated.
Updated by IEC 61850 TPWG 12 months ago
- Due date changed from 11/28/2023 to 12/12/2023
- Status changed from New to In Progress
Richard to propose change to clarify wording.
Updated by Richard Schimmel 11 months ago
- File Solution to redmine 6489 GOOSE performance resource.docx Solution to redmine 6489 GOOSE performance resource.docx added
Added solution with clarification (no technical change)
Updated by Michael Haecker 11 months ago
I agree to modify the introduction sentences of clauses 4.1.2 and 4.1.3 to "The DUT will subscribe to at least one element from each of the following GOOSE:"
BTW, typo in the proposed solution. The headline of clause 4.1.3 goes "not used for ping-pong".
Updated by IEC 61850 TPWG 11 months ago
- Due date changed from 01/09/2024 to 01/23/2024
title of 4.1.3 needs to be clarified. Richard to update attachment.
Updated by Richard Schimmel 10 months ago
- File Solution to redmine 6489 GOOSE performance resource (23Jan2024).docx Solution to redmine 6489 GOOSE performance resource (23Jan2024).docx added
Fixed the 4.1.3 Title "*not* used for ping-pong"
Updated by IEC 61850 TPWG 10 months ago
- Status changed from In Progress to Resolved
- Closed Reason Test Procedure Update added
- Closed Reason deleted (