CIM Issues #6346
[GMDM #14] Indicating starting point for feeder tracing
61970-301,, 61968-13
Description
The GMDM test model expressed the nominal containership of each ConductingEquipment child in a Feeder by means of the recently created Equipment.EquipmentContainer association with the AdditionalEquipmentContainer role. The decision was made not to use the Feeder.Terminal association for the support of energization training, however. An alternative was implemented which leveraged a proposed Feeder.ConnectivityNode association, specifying a node assumed to always be energized if the feeder was energized.
This issue is related to Issue #
Files
Decision
18-Sep-2024 Joint TF Hybrid Meeting:
Feeder.NormalHeadTerminal association's description must be changed to explain which direction to start tracing.
Current description is: "The normal head terminal or terminals of the feeder."
Should be updated to: "The normal head terminal (or terminals) of the feeder. The tracing is done towards the conducting equipment associated with the head terminal (or terminals)."
Approved for application in the model.
Related issues