Improvement #6248
There are controls between IEDs for automatic control functions, we need to be able to represent those controls in SCL (for configuration in SCT, data flow documentation...)
Status:
Resolved
Priority:
Normal
Assignee:
-
Category:
-
Start date:
02/03/2023
Due date:
% Done:
0%
Estimated time:
ID:
Source:
EDF
TF Unique ID:
WG10 Proposal:
Estimated Completion:
Solution to be included in Amendment 2.2
Discuss in Upcoming Meeting:
No
To discuss in WG10:
No
Short Proposal:
Standard(s):
IEC 61850-6
Needs More Information:
No
Assigned TF:
None
Description
Use cases detailled in the attached presentation
There are controls between IEDs for automatic control functions, for example:- 90-6 : The IED Controller performing the AATS (Automatic transfer between two source) needs to control XCBRs in other IEDs
- 7-4 : The IED Controller performing ARCO (Reactive power control) needs to control XSWIs in another IED
- 7-4 : The IED Controller performing ATCC (Automatic tap changer controller) needs to control YLTC in another IED
- Specify controls that an IED (performing automatic control functions) needs to perform for its logic
- Configure such controls of an IED, with a top/down approach, in the SCT, during the configuration process. Usefull also during the maintenance of the substation
- Document the data flows between IEDs, including the controls
- Document the binding of the controls to the internal addresses of the IED
Files
Proposal descriptions
In SCL, add elements equivalent to Inputs/Extref for Controls