09/24/2024

08:06 AM IEC 61850 User Feedback Task Force Bug #7001 (Resolved): Presence condition of DO in statistic Logical Nodes
It would seem logical that when a DO is multiple (instanciable, with Omulti/Mmulti) in a LN when it is used "non stat... Aurelie Dehouck

02/08/2024

02:43 AM IEC TC57 WG10 Future Work WG10 Future Work #6700 (New): Investigate to align to the new CIM model of transformers
The Model of PowerTransformers changed after CIM v15 (for the reasons explained bellow).
SCL model of CIM PowerTra...
Aurelie Dehouck

06/05/2023

09:47 AM IEC 61850 User Feedback Task Force Improvement #6248: There are controls between IEDs for automatic control functions, we need to be able to represent those controls in SCL (for configuration in SCT, data flow documentation...)
We will discuss this point and present a first draft of SCL evolutions during next WG10 meeting (during TF 7-5 / 7-50... Aurelie Dehouck

02/03/2023

04:11 AM IEC 61850 User Feedback Task Force Improvement #6248 (Resolved): There are controls between IEDs for automatic control functions, we need to be able to represent those controls in SCL (for configuration in SCT, data flow documentation...)
Use cases detailled in the attached presentation
There are controls between IEDs for automatic control functions, ...
Aurelie Dehouck

01/17/2023

03:05 AM IEC 61850 User Feedback Task Force Bug #6226 (Resolved): In the downgrading rules from ed 2.1 to ed 2.0 in part 6, it is mentionned to exclude ORS CDC (I.4.2.4). Why CDCs: CST, VSD and TCS that were also added in ed2.1 are not mentionned to be excluded also ?
61850-6 ed2.1 mention in I.4.2.4 "New CDC":
"The CDC ORS has been added to the list of the allowed CDCs. DOType wh...
Aurelie Dehouck

08/26/2022

08:21 AM IEC 61850 User Feedback Task Force Improvement #5955: Indicate typical SIUnit for every DO with CDC MV would help users + Add a dedicated attribute in NSD files instead of having it in the description ?
To include also in IEC 61400 Aurelie Dehouck
08:20 AM IEC 61850 User Feedback Task Force Improvement #5955 (Resolved): Indicate typical SIUnit for every DO with CDC MV would help users + Add a dedicated attribute in NSD files instead of having it in the description ?
In IEC61850-7-4, some DO with CDC MV have a SIUnit that is indicated in the description of the DO.
> Example : in MM...
Aurelie Dehouck