Project

General

Profile

Feature #6222

Parameters not available in standardized GAPC LN - SetNb

Added by Carlos Rodriguez del Castillo almost 2 years ago. Updated over 1 year ago.

Status:
In Progress
Priority:
Normal
Assignee:
-
Category:
Standard extension required
Start date:
11/24/2020
Due date:
05/24/2021 (over 3 years late)
% Done:

0%

Estimated time:
ID:
57
Source:
RTE
TF Unique ID:
57 # RTE
WG10 Proposal:
Estimated Completion:
Discuss in Upcoming Meeting:
No
To discuss in WG10:
No
Short Proposal:
Standard(s):

IEC 61850-7-4

Needs More Information:
Yes
Assigned TF:

Description

SetNb: generic enumerate for use cases where a dedicated enumerate is considered to be too specific. Use cases include:
  • Substation level functions for overload management: in case of overload in one feeder, it can be useful to either close or trip another feeder or the same feeder; or to issue an alarm. This corresponds to a setting with five cases that could be express with SetNb. Another SetNb could be used to identify the feeder to be opened or closed. It is preferred to add this as settings as it may changed depending on the operational conditions of the network.
  • Substation with several feeders connected to one generator hold by a different operator: the operator indicates, in case of de-energisation, the order of re-energisation of the generators. This depends of the state of generator and cannot be done by configuration.

[New parametres need to be modelled in GAPC LN. This issue refer to SetNb parameters, as explained in the attached documents by RTE.]


Files

20210326-RTE Use cases 622.docx 20210326-RTE Use cases 622.docx 20.2 KB Use case explanation Carlos Rodriguez del Castillo, 05/25/2021 10:14 AM
20210326-RTE Use cases 622_v2.docx 20210326-RTE Use cases 622_v2.docx 24 KB more details on use cases Maud Merley, 12/04/2022 11:56 PM

Related issues

Copied from IEC 61850 User Feedback Task Force - Feature #6221: Parameters not available in standardized GAPC LN - OnOffIn Progress11/24/202005/24/2021

Actions
Copied to IEC 61850 User Feedback Task Force - Feature #6223: Parameters not available in standardized GAPC LN - StrValIn Progress11/24/202005/24/2021

Actions

Also available in: Atom PDF