Feature #6222
Parameters not available in standardized GAPC LN - SetNb
Status:
In Progress
Priority:
Normal
Assignee:
-
Category:
Standard extension required
Start date:
11/24/2020
Due date:
05/24/2021 (over 3 years late)
% Done:
0%
Estimated time:
ID:
57
Source:
RTE
TF Unique ID:
57 # RTE
WG10 Proposal:
Estimated Completion:
Discuss in Upcoming Meeting:
No
To discuss in WG10:
No
Short Proposal:
Standard(s):
IEC 61850-7-4
Needs More Information:
Yes
Assigned TF:
Description
SetNb: generic enumerate for use cases where a dedicated enumerate is considered to be too specific. Use cases include:
- Substation level functions for overload management: in case of overload in one feeder, it can be useful to either close or trip another feeder or the same feeder; or to issue an alarm. This corresponds to a setting with five cases that could be express with SetNb. Another SetNb could be used to identify the feeder to be opened or closed. It is preferred to add this as settings as it may changed depending on the operational conditions of the network.
- Substation with several feeders connected to one generator hold by a different operator: the operator indicates, in case of de-energisation, the order of re-energisation of the generators. This depends of the state of generator and cannot be done by configuration.
[New parametres need to be modelled in GAPC LN. This issue refer to SetNb parameters, as explained in the attached documents by RTE.]
Files
Related issues
Updated by Carlos Rodriguez del Castillo almost 2 years ago
- Copied from Feature #6221: Parameters not available in standardized GAPC LN - OnOff added
Updated by Carlos Rodriguez del Castillo almost 2 years ago
- Copied to Feature #6223: Parameters not available in standardized GAPC LN - StrVal added
Updated by Vladan Cvejic almost 2 years ago
It is concluded that issue has to be presented and discussed on next joint meeting of TC57 & TC38 & TC95 in Lyon (May 25th, 2023). Will be presented by Maud Merley.