Issues #6203
sSvs6 - Test configuration does not consider available bandwidth
Description
Configuration requires: "DUT to subscribe the maximum number of SV streams, with
- 1) the maximum preferred variant of all preferred variants
- 2) and the remainder the lowest rate backwards compatible configuration.
-> the remainder configuration using the lowest rate backwards compatible - force to use I4U4 DataSets. The remaining bandwidth of 100MBit/s might not be sufficient to apply 2). 2 shall be flexible in defining the "remainder" - allowing also I1U0 or U0I1 with lowest rate in order to make the configuration fit in 100MBit/s (and maybe even 60% of 100MBit/s to have a reliable network).
Proposal: change 2) to "and the remainder the lowest rate with backwards compatible configuration or other configurations to fit in the remaining available bandwidth.
Files
Updated by Richard Schimmel 11 months ago
Disagree. Endusers need to know how many BW streams the DUT does support. As such it's easier to compare devices. Of course there is a bandwidth limitation.
Updated by IEC 61850 TPWG 11 months ago
- Due date changed from 01/10/2023 to 01/24/2023
Discuss when Richard is available.
Updated by IEC 61850 TPWG 11 months ago
- Due date changed from 01/24/2023 to 02/07/2023
- Assignee set to Richard Schimmel
Agreed as proposed by Thierry.
Updated by Richard Schimmel 11 months ago
- File Solution to redmine 6203 sSvs6.docx Solution to redmine 6203 sSvs6.docx added
- Initial Test Document set to TP1.2
- Test Case ID set to sSvs6
- 61850 Standard 9-2 added
Added solution as proposed