Issues #6203
sSvs6 - Test configuration does not consider available bandwidth
Description
Configuration requires: "DUT to subscribe the maximum number of SV streams, with
- 1) the maximum preferred variant of all preferred variants
- 2) and the remainder the lowest rate backwards compatible configuration.
-> the remainder configuration using the lowest rate backwards compatible - force to use I4U4 DataSets. The remaining bandwidth of 100MBit/s might not be sufficient to apply 2). 2 shall be flexible in defining the "remainder" - allowing also I1U0 or U0I1 with lowest rate in order to make the configuration fit in 100MBit/s (and maybe even 60% of 100MBit/s to have a reliable network).
Proposal: change 2) to "and the remainder the lowest rate with backwards compatible configuration or other configurations to fit in the remaining available bandwidth.
Files
Updated by Richard Schimmel almost 2 years ago
Disagree. Endusers need to know how many BW streams the DUT does support. As such it's easier to compare devices. Of course there is a bandwidth limitation.
Updated by IEC 61850 TPWG almost 2 years ago
- Due date changed from 01/10/2023 to 01/24/2023
Discuss when Richard is available.
Updated by IEC 61850 TPWG almost 2 years ago
- Due date changed from 01/24/2023 to 02/07/2023
- Assignee set to Richard Schimmel
Agreed as proposed by Thierry.
Updated by Richard Schimmel almost 2 years ago
- File Solution to redmine 6203 sSvs6.docx Solution to redmine 6203 sSvs6.docx added
- Initial Test Document set to TP1.2
- Test Case ID set to sSvs6
- 61850 Standard 9-2 added
Added solution as proposed
Updated by Richard Schimmel 9 months ago
- Status changed from Resolved to Closed
- Updated Test Document set to TP1.3