Project

General

Profile

Issues #6157

sCnf/sMdl not applicable for test equipment

Added by Richard Schimmel about 2 years ago. Updated 9 months ago.

Status:
Closed
Priority:
Normal
Due date:
11/15/2022
Discuss in Upcoming Meeting:
No
Clause Reference:
61850 Standard:
6
Triggering Tissue:
Final Decision:
Initial Test Document:
Updated Test Document:
Test Case ID:
Closed Reason:
Test Procedure Update
Triggering Tissue 2:
Triggering Tissue 3:

Description

PIXIT As9 indicates the DUT is test equipment or not. Test equipment has no ICD file. Test equipment imports existing SCD/IID from other manufacturers. For Amd1 we required the DUT has an ICT tool to export IID/ICD and import SCD file. Test equipment only imports SCD file.
We propose that for test equipment all the sCnf/sMdl test cases are not applicable, except "import SCD" sCnf5
For example add in clause A2 and A3 a general paragraph: The following test cases are not applicable for test equipment


Files

Also available in: Atom PDF