Project

General

Profile

Issues #6157

sCnf/sMdl not applicable for test equipment

Added by Richard Schimmel over 1 year ago. Updated 27 days ago.

Status:
Closed
Priority:
Normal
Due date:
11/15/2022
Discuss in Upcoming Meeting:
No
Clause Reference:
61850 Standard:
6
Triggering Tissue:
Final Decision:
Initial Test Document:
Updated Test Document:
Test Case ID:
Closed Reason:
Test Procedure Update
Triggering Tissue 2:
Triggering Tissue 3:

Description

PIXIT As9 indicates the DUT is test equipment or not. Test equipment has no ICD file. Test equipment imports existing SCD/IID from other manufacturers. For Amd1 we required the DUT has an ICT tool to export IID/ICD and import SCD file. Test equipment only imports SCD file.
We propose that for test equipment all the sCnf/sMdl test cases are not applicable, except "import SCD" sCnf5
For example add in clause A2 and A3 a general paragraph: The following test cases are not applicable for test equipment


Files

#1

Updated by IEC 61850 TPWG over 1 year ago

  • Due date set to 11/15/2022
  • Status changed from New to In Progress
  • Assignee set to Richard Schimmel

Accepted.

Add in clause A2 and A3 a general paragraph: The following test cases are not applicable for test equipment, conditional on PIXIT As9.

Richard to draft.

#3

Updated by IEC 61850 TPWG over 1 year ago

  • Status changed from In Progress to Resolved
  • Closed Reason Test Procedure Update added
  • Closed Reason deleted (--Not Set---)
#4

Updated by Richard Schimmel 27 days ago

  • Status changed from Resolved to Closed
  • Updated Test Document set to TP1.3

Also available in: Atom PDF