Project

General

Profile

Issues #5905

sSrvN4 is mandatory, used SetDataValues service is optional in PICS and may not be not supported

Added by christian zehnder over 2 years ago. Updated 9 months ago.

Status:
Closed
Priority:
Normal
Due date:
09/06/2022
Discuss in Upcoming Meeting:
No
Clause Reference:
61850 Standard:
7-2
Triggering Tissue:
Final Decision:
Initial Test Document:
Updated Test Document:
Test Case ID:
Closed Reason:
Test Procedure Update
Triggering Tissue 2:
Triggering Tissue 3:

Description

sSrvN4 is mandatory for Ed.2_Rev2p0p6 and Ed2Amd1_Rev1p1:

Expected result
1. DUT sends response with data access error “object-access-denied”
Test description
1. Client sends a SetDataValues request with a read-only FCDA

I wonder why a possible not supported service is mandatory to test. Some other sSrvx are optional based on PICS entry. I see it then as how a server handles a "unknown" write request.
Currently tested server, not supporting service, responds correctly.


Files

#1

Updated by IEC 61850 TPWG over 2 years ago

  • Due date set to 09/06/2022
  • Status changed from New to In Progress
  • Assignee set to Richard Schimmel
  • Closed Reason Test Procedure Update added
  • Closed Reason deleted (--Not Set---)

Keep as mandatory.

reject or error message from device that does not support setDataValue should be considered "pass".

#3

Updated by IEC 61850 TPWG about 2 years ago

#4

Updated by Richard Schimmel 9 months ago

  • Status changed from Resolved to Closed
  • Updated Test Document set to TP1.3

Also available in: Atom PDF